South Australia variation · NCC 2022 Volume One

SA D3D16 Thresholds

Part D3 Construction of exits

Open on NCC Online ↗

Delete clause D3D16 and insert SA D3D16 as follows:

(1) The threshold of a doorway must not incorporate a step or ramp at any point closer to the doorway than the width of the door leaf unless—

in patient care areas in a Class 9a health-care building, the door sill is not more than 25 mm above the finished floor level to which the doorway opens; or

in resident use areas a Class 9c building, a ramp is provided with a maximum gradient of 1:8 for a maximum height of 25 mm over the threshold; or

in a building required to be accessible by Part D4, the doorway—

opens to a road or open space; and

is provided with a threshold ramp or step ramp in accordance with AS 1428.1; or

in other cases—

the doorway opens to a road or open space, external stair landing or external balcony; and

the door sill is not more than 190 mm above the finished surface of the ground, balcony, or the like, to which the doorway opens.

(2) Notwithstanding the requirements of (1), where necessary due to the operational requirements of the building, a doorway serving a farm building may incorporate a step that is no more than 700 mm above the finished floor level.

Not in NCC 2025. No SA D3D16 in NCC 2025 Volume One.