South Australia variation · NCC 2022 Volume One

SA D3D25 Swinging doors

Part D3 Construction of exits · varies D3D25 Swinging doors

Open on NCC Online ↗

Delete subclause D3D25(1) and insert SA D3D25(1) as follows:

(1) A swinging door in a required exit or forming part of a required exit—

must not encroach—

at any part of its swing by more than 500 mm on the required width (including any landings) of a required stairway, ramp or passageway if it is likely to impede the path of travel of the people already using the exit; and

when fully open, by more than 100 mm on the required width of the required exit; and

must swing in the direction of egress unless—

it serves a building or part with a floor area not more than 200 m2, it is the only required exit from the building or part and it is fitted with a device for holding it in the open position; or

it serves a sanitary compartment or airlock (in which case it may swing in either direction); or

it serves a farm building; and

must not otherwise impede the path or direction of egress.

Not in NCC 2025. No SA D3D25 in NCC 2025 Volume One.

The national clause