Table C3D3 Maximum size of fire compartments or atria
Part C3 Compartmentation and separation
| Classification | Type A construction | Type B construction | Type C construction |
|---|---|---|---|
| 5, 9b or 9c | Max floor area—8 000 m2 | Max floor area—5 500 m2 | Max floor area—3 000 m2 |
| Max volume—48 000 m3 | Max volume—33 000 m3 | max volume—18 000 m3 | |
| 6, 7, 8 or 9a (except for patient care areas) | Max floor area—5 000 m2 | Max floor area—3 500 m2 | Max floor area—2 000 m2 |
| Max volume—30 000 m3 | Max volume—21 000 m3 | Max volume—12 000 m3 |
Table Notes
See C3D6 for maximum size of compartments in patient care areas in Class 9a health-care buildings.
Table for C3D3 General floor area and volume limitations
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table C3D3.