Table · NCC 2025 Volume One

Table C3D3 Maximum size of fire compartments or atria

Part C3 Compartmentation and separation

Open Table C3D3 on NCC Online ↗
ClassificationType A constructionType B constructionType C construction
5, 9b or 9cMax floor area —8 000 m2Max floor area —5 500 m2Max floor area —3 000 m2
Max volume —48 000 m3Max volume —33 000 m3max volume —18 000 m3
6, 7, 8 or 9a (except for patient care areas)Max floor area —5 000 m2Max floor area —3 500 m2Max floor area —2 000 m2
Max volume —30 000 m3Max volume —21 000 m3Max volume —12 000 m3

Table Notes

See C3D6 for maximum size of compartments in patient care areas in Class 9a health-care buildings.

Table for C3D3 General floor area and volume limitations

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table C3D3.