Table · NCC 2022 Volume One
Table F3V1a Risk factors and scores
Part F3 Roof and wall cladding
| Risk factor | Category | Risk severity | Score |
|---|---|---|---|
| Wind region | Region A0-5 (AS/NZS 1170.2) | Low to medium | 0 |
| Region C (AS/NZS 1170.2) | High | 1 | |
| Region D (AS/NZS 1170.2) | Very high | 2 | |
| Number of storeys | One storey | Low | 0 |
| Two storeys in part | Medium | 1 | |
| Two storeys | High | 2 | |
| More than two storeys | Very high | 4 | |
| Roof/wall junctions | Roof-to-wall junctions fully protected | Low | 0 |
| Roof-to-wall junctions partially exposed | Medium | 1 | |
| Roof-to-wall junctions fully exposed | High | 3 | |
| Roof elements finishing within the boundaries formed by the external walls | Very high | 5 | |
| Eaves width | More than 600 mm for single storey | Low | 0 |
| 451-600 mm for single storey | Medium | 1 | |
| 101-450 mm for single storey | High | 2 | |
| 0-100 mm for single storey | Very high | 5 | |
| Envelope complexity | Simple shape with single cladding type | Low | 0 |
| Complex shape with not more than two cladding types | Medium | 1 | |
| Complex shape with more than two cladding types | High | 3 | |
| As for high risk but with fully exposed roof-to-wall junctions | Very high | 6 | |
| Decks, porches and balconies | None | Low | 0 |
| Fully covered in plan view by roof | Medium | 2 | |
| Balcony exposed in plan view at first floor level | High | 4 | |
| Balcony exposed in plan view at second floor level or above | Very high | 6 |
Region B1-2 (AS/NZS 1170.2)
More than 600 mm for two storey
451-600 mm for two storey
More than 600 mm for above two storey
0-450 mm for two storey
Less than 600 mm for above two storey
Timber slat deck or porch at ground level
Timber slat deck attached at first or second floor level
Balcony cantilevered at first floor level
Balcony cantilevered at second floor level or above
Table Notes
Eaves width is measured horizontally from the external face of any wall cladding to the outer edge of any overhang, including fascia and external gutters.
Barriers to prevent falling and parapets are considered as 0 mm eaves.
Table for F3V1 Weatherproofing
Not in NCC 2025. No Table F3V1a in NCC 2025 Volume One.