Table · NCC 2022 Volume One
Table J3D12j Conductance factors — climate zones 2 to 7
| Type of factor | Climate zone 2 | Climate zone 3 | Climate zone 4 | Climate zone 5 | Climate zone 6 | Climate zone 7 |
|---|---|---|---|---|---|---|
| Room type multiplier (for bedroom and unconditioned areas) (RS) | 0.40 | 0.56 | 0.71 | 0.91 | 0.87 | 1.11 |
| Frame solar absorptance multiplier (for metal frame windows) (FS) SA ≤ 0.40 | 1.00 | 0.89 | 0.87 | 0.85 | 0.74 | 0.86 |
| Frame solar absorptance multiplier (for metal frame windows) (FS) SA > 0.40 to < 0.68 | 1.06 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| Frame solar absorptance multiplier (for metal frame windows) (FS) SA ≥ 0.68 | 1.22 | 1.18 | 1.22 | 1.24 | 1.22 | 1.32 |
| Floor factor for tiled or vinyl covered floors (HS) | 1.06 | 1.06 | 1.13 | 1.13 | 1.04 | 1.21 |
| Floor factor for other than tiled or vinyl covered floors (HS) | 0.97 | 0.97 | 0.94 | 0.94 | 0.94 | 0.90 |
Table Notes
Interpolation is allowed for values between those shown.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D12j.