NCC 2022 Volume One
Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building
75 clauses · Open on NCC Online ↗
- J3D1 Deemed-to-Satisfy Provisions NSWWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirements J1P1 to J1P4 are satisfied by complying with— J2D2; and J3D2 to J3D15; and…
- J3D2 Application of Part NSWThe Deemed-to-Satisfy Provisions of this Part apply to building elements forming the external building fabric and domestic services of a…
- J3D3 Reducing heating and cooling loads of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building using house energy rating software NSWThe sole-occupancy units of a Class 2 building or a Class 4 part of a building must— for reducing the heating or cooling loads— collectively achieve…
- Table J3D4 Minimum ceiling fan requirements in climate zones 1, 2, 3 and 5Size of room (m2) | Minimum number and diameter (mm) of ceiling fans required for a bedroom in climate zones 1, 2 and 3 | Minimum number and…
- J3D4 Ceiling fans in a sole-occupancy unit of a Class 2 building or a Class 4 part of a building NSWCeiling fans must be installed in accordance with Table J3D4 in— climate zones 1, 2 and 3; and climate zone 5 in New South Wales and Queensland. (2)…
- J3D5 Roof thermal breaks of a sole-occupancy unit of a Class 2 building or a Class 4 part of a buildingA roof that— has metal sheet roofing directly fixed to metal purlins, metal rafters or metal battens; and does not have a ceiling lining or has a…
- J3D6 Wall thermal breaks of a sole-occupancy unit of a Class 2 building or a Class 4 part of a buildingA metal-framed wall that forms part of the building envelope must have a thermal break, consisting of a material with an R-Value of not less than…
- Table J3D7a Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 1Reflective insulation under-roof | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA > 0.42 to ≤ 0.53 | SA > 0.53 to ≤ 0.64 Yes | 1.0 | 1.5…
- Table J3D7b Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 1Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA >…
- Table J3D7c Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 1Reflective insulation under-roof | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA > 0.42 to ≤ 0.53 | SA > 0.53 to ≤ 0.64 Yes | 1.5 | 1.5…
- Table J3D7d Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 2Reflective insulation under-roof | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA > 0.42 to ≤ 0.53 | SA > 0.53 to ≤ 0.64 Yes | 2.0 | 2.5…
- Table J3D7e Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 2Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA >…
- Table J3D7f Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 2Reflective insulation under-roof | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA > 0.42 to ≤ 0.53 | SA > 0.53 to ≤ 0.64 Yes | 2.5 | 2.5…
- Table J3D7g Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 3Reflective insulation under-roof | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA > 0.42 to ≤ 0.53 | SA > 0.53 to ≤ 0.64 Yes | 2.0 | 2.0…
- Table J3D7h Timber-framed pitched roof with horizontal ceiling — minimum R-Values for ceiling insulation: climate zone 3Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA >…
- Table J3D7i Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 3Reflective insulation under-roof | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA > 0.42 to ≤ 0.53 | SA > 0.53 to ≤ 0.64 Yes | 2.0 | 2.0…
- Table J3D7j Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 4Reflective insulation under-roof | ≤ 0.64 Yes | 2.0 No | 2.5 Table Notes SA = solar absorptance. The R-Value of reflective insulation is not to be…
- Table J3D7k Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 4Roof ventilation | Reflective insulation under- roof | Under-roof insulation R-Value | SA ≤ 0.23 | SA > 0.23 to ≤ 0.64 Vented | Yes | < 0.5 | 3.0 |…
- Table J3D7l Timber-framed flat, skillion or cathedral timber roof — minimum R-Value for ceiling insulation: climate zone 4Reflective insulation under-roof | SA ≤ 0.64 Yes | 3.0 No | 3.5 Table Notes SA = solar absorptance. The R-Value can be achieved by installing…
- Table J3D7m Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 5Reflective insulation under-roof | SA ≤ 0.42 | SA > 0.42 to ≤ 0.64 Yes | 3.0 | 3.5 No | 4.0 | 4.0 Table Notes SA = solar absorptance. The R-Value of…
- Table J3D7n Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 5Roof ventilation | Reflective insulation under- roof | Under-roof insulation R-Value | SA ≤ 0.42 | SA > 0.42 to ≤ 0.64 Vented | Yes | < 0.5 | 3.0 |…
- Table J3D7o Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 5Reflective insulation under- roof | R-Value Yes | 2.5 No | 3.0 Table Notes The R-Value can be achieved by installing insulation under the roof or on…
- Table J3D7p Flat concrete roof — minimum R-Value for ceiling insulation: climate zones 7 and 8Reflective insulation under-roof | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA > 0.42 to ≤ 0.53 | SA > 0.53 to ≤ 0.64 | SA > 0.64 to…
- Table J3D7q Timber-framed pitched roof with flat ceiling — minimum R-Value for ceiling insulation: climate zones 7 and 8Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA >…
- Table J3D7r Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zones 7 and 8Reflective insulation under-roof | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA > 0.42 to ≤ 0.53 | SA > 0.53 to ≤ 0.64 | SA > 0.64 to…
- Table J3D7s Metal-framed pitched roof with horizontal ceiling — minimum Total R-Value of ceiling to account for thermal bridgingCeiling insulation R-Value from Tables J3D7a to J3D7r and J3D7(1)(f) as applicable | Minimum Total R-Value to account for thermal bridging 1.5 |…
- Table J3D7t Metal-framed flat, skillion or cathedral roof — minimum Total R-Value to account for thermal bridgingCeiling insulation R-Value from Tables J3D7a to J3D7r, and J3D7(1)(f) as applicable | Minimum Total R-Value to account for thermal bridging: heat…
- Table J3D7u Metal-framed flat, skillion or cathedral roof – thermal bridging mitigationMinimum ceiling R-Value from Tables J3D7a to J3D7r, and J3D7(1)(f) as applicable | Option 1– increase insulation between roof frame members to…
- Table J3D7v Direction of heat flowClimate zone | Direction of heat flow 1 | Down 2 – altitude less than 300 m | Down 2 – altitude 300 m or more | Down and up 3 | Down and up 4 | Up 5…
- Table J3D7w Adjusted minimum R-Value of ceiling insulation required to compensate for loss of ceiling insulation areaPercentage of ceiling area uninsulated | Minimum R-Value of ceiling insulation required to satisfy J3D7(1) and J3D7(3) 1.0 | 1.5 | 2.0 | 2.5 | 3.0 |…
- Table J3D7x Total R-Values for roofs constructed with insulated sandwich panelsClimate zone | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA > 0.42 to ≤ 0.53 | SA > 0.53 to ≤ 0.64 | SA > 0.64 to ≤ 0.73 | SA > 0.73…
- J3D7 Roofs and ceilings of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building NSWRoof and ceiling insulation must achieve the minimum R-Value— in climate zone 1, in accordance with Tables J3D7a, J3D7b and J3D7c as applicable; and…
- Table J3D8a Solar absorptance – climate zones 1 to 6Climate zone | Opaque external wall to net floor area ratio | Permitted solar absorptance 1 and 3 | < 45% | ≤ 0.8 ≥ 45% | ≤ 0.35 2 | < 35% | Any ≥…
- Table J3D8b Solar absorptance – climate zones 7 and 8Opaque external wall to net floor area ratio | Shading device overhang (mm) ≥ 0 to < 600 | ≥ 600 to < 900 | ≥ 900 to < 1200 | ≥ 1200 < 20% | Any |…
- J3D8 External walls of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building NSWThe Total R-Value of an external wall— in climate zones 1, 2, 3, 5 and 6— where the ratio of the area of opaque external walls to the floor area of…
- Table J3D9 Maximum wall-glazing construction solar admittanceClimate zone | Eastern aspect solar admittance | Northern aspect solar admittance | Southern aspect solar admittance | Western aspect solar…
- J3D9 Wall-glazing construction of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building NSWThe Total System U-Value of wall-glazing construction that forms part of the external building fabric must not be greater than— in climate zones 1…
- J3D10 Floors of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building NSWWhere a sole-occupancy unit of a Class 2 building or a Class 4 part of a building has a concrete floor above an unenclosed carpark, undercroft, or…
- Table J3D11a Maximum conductance to solar heat gain ratio (CU/CSHGC)Climate zone | Maximum conductance to solar heat gain ratio (CU/CSHGC) 2 | 16.95 3 | 19.88 4 | 13.34 5 | 11.83 6 | 6.27 7 | 12.90 8 | 12.90
- Table J3D11b Orientation sector winter exposure factor (EW): climate zone 2P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 1.49 | 1.61 | 1.23 | 0.96 | 0.68 | 1.03 | 1.37 | 1.71…
- Table J3D11c Orientation sector winter exposure factor (EW): climate zone 3P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 0.90 | 1.10 | 0.88 | 0.69 | 0.50 | 0.58 | 0.67 | 0.91…
- Table J3D11d Orientation sector winter exposure factor (EW): climate zone 4P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 1.58 | 1.66 | 1.16 | 0.93 | 0.70 | 0.78 | 0.85 | 1.38…
- Table J3D11e Orientation sector winter exposure factor (EW): climate zone 5P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 1.61 | 1.34 | 1.08 | 0.87 | 0.67 | 0.76 | 0.85 | 1.23…
- Table J3D11f Orientation sector winter exposure factor (EW): climate zone 6P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 3.04 | 2.50 | 1.52 | 1.51 | 1.51 | 1.63 | 1.76 | 2.75…
- Table J3D11g Orientation sector winter exposure factor (EW): climate zones 7 and 8P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 1.66 | 1.53 | 0.90 | 0.82 | 0.74 | 0.78 | 0.83 | 1.43…
- Table J3D11h Conductance and radiation factors: climate zone 2Type of factor | Factor Bedroom conduction weighting factor (BC) | 0.43 Room type multiplier (for bedroom and unconditioned areas) (RW) | 1.00…
- Table J3D11i Conductance and radiation factors: climate zone 3Type of factor | Factor Bedroom conduction weighting factor (BC) | 0.42 Room type multiplier (for bedroom and unconditioned areas) (RW) | 1.00…
- Table J3D11j Conductance and radiation factors: climate zone 4Type of factor | Factor Bedroom conduction weighting factor (BC) | 0.70 Room type multiplier (for bedroom and unconditioned areas) (RW) | 1.00…
- Table J3D11k Conductance and radiation factors: climate zone 5Type of factor | Factor Bedroom conduction weighting factor (BC) | 0.63 Room type multiplier (for bedroom and unconditioned areas) (RW) | 1.10…
- Table J3D11l Conductance and radiation factors: climate zone 6Type of factor | Factor Bedroom conduction weighting factor (BC) | 0.81 Room type multiplier (for bedroom and unconditioned areas) (RW) | 1.00…
- Table J3D11m Conductance and radiation factors: climate zones 7 and 8Type of factor | Factor Bedroom conduction weighting factor (BC) | 0.60 Room type multiplier (for bedroom and unconditioned areas) (RW) | 1.00…
- Table J3D11n Orientation sector conductance factor (OC)Climate zone | North | North east | East | South east | South | South west | West | North west 2 | 1.70 | 1.34 | 0.98 | 0.84 | 0.70 | 0.90 | 1.10 |…
- Table J3D11o Frame factor (FW) — climate zone 2Frame solar absorptance | Factor ≤ 0.40 | 0.97 > 0.40 to < 0.68 | 1.00 ≥ 0.68 | 1.08 Table Notes Interpolation is allowed for values between those…
- Table J3D11p Frame factor (FW) — climate zone 3Frame solar absorptance | Factor ≤ 0.40 | 0.98 > 0.40 to < 0.68 | 1.00 ≥ 0.68 | 1.05 Table Notes Interpolation is allowed for values between those…
- Table J3D11q Frame factor (FW) — climate zone 4Frame solar absorptance | Factor ≤ 0.40 | 0.99 > 0.40 to < 0.68 | 1.00 ≥ 0.68 | 1.01 Table Notes Interpolation is allowed for values between those…
- Table J3D11r Frame factor (FW) — climate zone 5Frame solar absorptance | Factor ≤ 0.40 | 1.00 > 0.40 to < 0.68 | 1.00 ≥ 0.68 | 1.01 Table Notes Interpolation is allowed for values between those…
- Table J3D11s Frame factor (FW) — climate zone 6Frame solar absorptance | Factor ≤ 0.40 | 0.92 > 0.40 to < 0.68 | 1.00 ≥ 0.68 | 1.13 Table Notes Interpolation is allowed for values between those…
- Table J3D11t Frame factor (FW) — climate zones 7 and 8Frame solar absorptance | Factor ≤ 0.40 | 0.97 > 0.40 to < 0.68 | 1.00 ≥ 0.68 | 1.01 Table Notes Interpolation is allowed for values between those…
- J3D11 External winter glazing of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building NSWIn climate zones 2 to 8, the ratio of the conductance (CU) and solar heat gain (CSHGC) of the glazing of each storey, including any mezzanine, of a…
- Table J3D12a Constant for Solar Heat Gain (CSHGC) — climate zones 1 to 7% Ventilation opening area per m2 | Climate zone 1 | Climate zone 2 | Climate zone 3 | Climate zone 4 | Climate zone 5 | Climate zone 6 | Climate…
- Table J3D12b Orientation sector summer exposure factor (Es) — climate zone 1P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 0.62 | 0.76 | 0.79 | 0.75 | 0.52 | 0.89 | 1.06 | 0.85…
- Table J3D12c Orientation sector summer exposure factor (Es) — climate zone 2P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 0.65 | 1.16 | 1.59 | 1.20 | 0.73 | 1.30 | 1.77 | 1.23…
- Table J3D12d Orientation sector summer exposure factor (Es) — climate zone 3P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 0.80 | 1.26 | 1.41 | 1.38 | 0.89 | 1.33 | 1.29 | 1.20…
- Table J3D12e Orientation sector summer exposure factor (Es) — climate zone 4P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 0.79 | 1.13 | 1.12 | 1.05 | 0.68 | 1.14 | 1.44 | 1.23…
- Table J3D12f Orientation sector summer exposure factor (Es) — climate zone 5P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 0.82 | 1.20 | 1.31 | 1.06 | 0.82 | 1.04 | 1.30 | 1.16…
- Table J3D12g Orientation sector summer exposure factor (Es) — climate zone 6P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 2.18 | 2.75 | 2.88 | 2.22 | 1.59 | 2.46 | 2.91 | 2.90…
- Table J3D12h Orientation sector summer exposure factor (Es) — climate zone 7P/H | North | North east | East | South east | South | South west | West | North west 0.00 | 0.89 | 1.06 | 1.06 | 0.93 | 0.70 | 0.91 | 1.06 | 1.07…
- Table J3D12i Conductance factors — climate zone 1Factor | Value Room type multiplier (for bedroom and unconditioned areas) (RS) | 0.32 Frame solar absorptance multiplier Frame SA = 0.3 up to 0.4…
- Table J3D12j Conductance factors — climate zones 2 to 7Type of factor | Climate zone 2 | Climate zone 3 | Climate zone 4 | Climate zone 5 | Climate zone 6 | Climate zone 7 Room type multiplier (for…
- J3D12 External summer glazing of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building NSWIn climate zones 1 to 7, the aggregate solar heat gain of the glazing in each storey, including any mezzanine, of a sole-occupancy unit of a Class 2…
- J3D13 Shading of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building NSWWhere shading is required to comply with J3D11 or J3D12, it must— be provided by an external permanent projection, such as a verandah, balcony,…
- Table J3D14a Floor area adjustment factor for a sole-occupancy unit of a Class 2 building or a Class 4 part of a buildingTotal floor area m2 | Floor area factor | Total floor area m2 | Floor area factor | Total floor area m2 | Floor area factor | Total floor area m2 |…
- Table J3D14b Energy factor for a sole-occupancy unit of a Class 2 building or a Class 4 part of a buildingClimate zone | ACT | NSW | NT | QLD | SA | TAS | Vic | WA 1 | — | — | 2.73 | 3.95 | — | — | — | 4.64 2 | — | 1.88 | — | 2.54 | — | — | — | — 3 | — |…
- J3D14 Net equivalent energy usage of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building NSWThe net equivalent energy usage of a sole-occupancy unit of a Class 2 building or Class 4 part of a building, calculated in accordance with (a),…
- J3D15 Net equivalent energy usage for a sole-occupancy unit of a Class 2 building or Class 4 part of building – home energy rating software NSWA sole-occupancy unit of a Class 2 building or a Class 4 part of a building must achieve a whole-of-home rating of not less than 50 using house…