Table · NCC 2022 Volume One

Table S21C2 Fire load (MW)

Specification 21 Smoke exhaust systems

Open Table S21C2 on NCC Online ↗
ClassificationFire load (MW) for unsprinklered buildingsFire load (MW) for sprinklered buildings
Class 2, 3 or 551.5
Class 6105
Class 7 or 8155
Class 9 — generally51.5
Class 9b buildings covered by Part I1 (see Note) or exhibition halls105

Table Notes

If the smoke reservoir above the stage is smoke separated from the audience area, the fire load specified applies to the stage area only and the fire load for the audience area is as per Class 9 generally.

Table for S21C2 Smoke exhaust capacity

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S21C2.