Table · NCC 2025 Volume One
Table S21C2 Fire load (MW)
Specification 21 Smoke exhaust systems
| Classification | Fire load (MW) for unsprinklered buildings | Fire load (MW) for sprinklered buildings |
|---|---|---|
| Class 2, 3 or 5 | 5 | 1.5 |
| Class 6 | 10 | 5 |
| Class 7 or 8 | 15 | 5 |
| Class 9 — generally | 5 | 1.5 |
| Class 9b buildings covered by Part I1 (see Note) or exhibition halls | 10 | 5 |
Table Notes
If the smoke reservoir above the stage is smoke separated from the audience area, the fire load specified applies to the stage area only and the fire load for the audience area is as per Class 9 generally.
Table for S21C2 Smoke exhaust capacity
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S21C2.