Table · NCC 2022 Volume One

Table S35C2g Occupancy and operation profiles of a Class 9a ward area

Specification 35 Modelling profiles for J1V3

Open Table S35C2g on NCC Online ↗
Time period (local standard time)Occupancy (Daily)Artificial lighting (Daily)Air-conditioning (Daily)
12:00am to 1:00am70%5%On
1:00am to 2:00am70%5%On
2:00am to 3:00am70%5%On
3:00am to 4:00am70%5%On
4:00am to 5:00am70%5%On
5:00am to 6:00am70%25%On
6:00am to 7:00am70%80%On
7:00am to 8:00am70%80%On
8:00am to 9:00am70%50%On
9:00am to 10:00am70%20%On
10:00am to 11:00am70%20%On
11:00am to 12:00pm70%20%On
12:00pm to 1:00pm70%20%On
1:00pm to 2:00pm70%20%On
2:00pm to 3:00pm70%20%On
3:00pm to 4:00pm70%20%On
4:00pm to 5:00pm70%20%On
5:00pm to 6:00pm70%50%On
6:00pm to 7:00pm70%50%On
7:00pm to 8:00pm70%50%On
8:00pm to 9:00pm70%50%On
9:00pm to 10:00pm70%50%On
10:00pm to 11:00pm70%50%On
11:00pm to 12:00am70%5%On

Table Notes

The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building.

The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J7.

The air-conditioning profile is expressed as the plant status.

Table for S35C2 Modelling profiles

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S35C2g.