S35C2 Modelling profiles
Specification 35 Modelling profiles for J1V3 · NCC 2019: Spec JVc: 2
(1) The air-conditioning, must be modelled on the basis of—
the daily occupancy and operation profiles in Tables S35C2a, S35C2b, S35C2c, S35C2d, S35C2e, S35C2f, S35C2g, S35C2h, S35C2i, S35C2j and S35C2k; and
the internal heat gains in a building—
from occupants and hot meals, in accordance with one of the options in Table S35C2n; and
from appliances and equipment, in accordance with Table S35C2l; and
from artificial lighting, determined in accordance with (2).
(2) The artificial lighting, must be modelled on the basis of the proposed level of artificial lighting in the building with the daily profile in Tables S35C2a, S35C2b, S35C2c, S35C2d, S35C2e, S35C2f, S35C2g, S35C2h, S35C2i, S35C2j and S35C2k.
(3) The heated water supply, must be modelled on the basis of the consumption rates of Table S35C2m.
Table S35C2a Occupancy and operation profiles of a Class 2 common area
Time period (local standard time)
Occupancy (Daily)
Artificial lighting (Daily)
Appliances and equipment (Daily)
Air-conditioning (Daily)
12:00am to 1:00am
0%
30%
0%
On
1:00am to 2:00am
0%
30%
0%
On
2:00am to 3:00am
0%
30%
0%
On
3:00am to 4:00am
0%
30%
0%
On
4:00am to 5:00am
0%
30%
0%
On
5:00am to 6:00am
0%
30%
0%
On
6:00am to 7:00am
0%
50%
0%
On
7:00am to 8:00am
0%
50%
0%
On
8:00am to 9:00am
0%
50%
0%
On
9:00am to 10:00am
0%
50%
0%
On
10:00am to 11:00am
0%
50%
0%
On
11:00am to 12:00pm
0%
50%
0%
On
12:00pm to 1:00pm
0%
50%
0%
On
1:00pm to 2:00pm
0%
50%
0%
On
2:00pm to 3:00pm
0%
50%
0%
On
3:00pm to 4:00pm
0%
50%
0%
On
4:00pm to 5:00pm
0%
50%
0%
On
5:00pm to 6:00pm
0%
50%
0%
On
6:00pm to 7:00pm
0%
50%
0%
On
7:00pm to 8:00pm
0%
50%
0%
On
8:00pm to 9:00pm
0%
50%
0%
On
9:00pm to 10:00pm
0%
50%
0%
On
10:00pm to 11:00pm
0%
50%
0%
On
11:00pm to 12:00am
0%
30%
0%
On
Table Notes
The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J7.
Table S35C2b Occupancy and operation profiles of a Class 3 hotel
Time period (local standard time)
Occupancy (Daily)
Artificial lighting (Daily)
Appliances and equipment (Daily)
Air-conditioning (Daily)
12:00am to 1:00am
90%
5%
20%
On
1:00am to 2:00am
90%
5%
20%
On
2:00am to 3:00am
90%
5%
15%
On
3:00am to 4:00am
90%
5%
15%
On
4:00am to 5:00am
90%
5%
15%
On
5:00am to 6:00am
80%
25%
15%
On
6:00am to 7:00am
70%
80%
40%
On
7:00am to 8:00am
60%
80%
80%
On
8:00am to 9:00am
60%
50%
50%
On
9:00am to 10:00am
30%
20%
30%
On
10:00am to 11:00am
10%
20%
20%
Off
11:00am to 12:00pm
10%
20%
20%
Off
12:00pm to 1:00pm
10%
20%
20%
Off
1:00pm to 2:00pm
10%
20%
20%
Off
2:00pm to 3:00pm
10%
20%
20%
Off
3:00pm to 4:00pm
10%
20%
20%
Off
4:00pm to 5:00pm
20%
20%
20%
On
5:00pm to 6:00pm
30%
50%
40%
On
6:00pm to 7:00pm
40%
50%
40%
On
7:00pm to 8:00pm
50%
50%
50%
On
8:00pm to 9:00pm
60%
50%
60%
On
9:00pm to 10:00pm
70%
50%
60%
On
10:00pm to 11:00pm
70%
50%
40%
On
11:00pm to 12:00am
90%
50%
20%
On
Table Notes
The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the Class 3 building.
The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J7.
The air-conditioning profile is expressed as the plant status.
Table S35C2c Weekday occupancy and operation profiles of a Class 5 building, a Class 7 warehouse, a Class 8 Laboratory or a Class 9a clinic, day surgery or procedure unit
Time period (local standard time)
Occupancy (Monday to Friday)
Artificial lighting (Monday to Friday)
Appliances and equipment (Monday to Friday)
Air-conditioning (Monday to Friday)
12:00am to 1:00am
0%
15%
25%
Off
1:00am to 2:00am
0%
15%
25%
Off
2:00am to 3:00am
0%
15%
25%
Off
3:00am to 4:00am
0%
15%
25%
Off
4:00am to 5:00am
0%
15%
25%
Off
5:00am to 6:00am
0%
15%
25%
Off
6:00am to 7:00am
0%
15%
25%
Off
7:00am to 8:00am
10%
40%
65%
On
8:00am to 9:00am
20%
90%
80%
On
9:00am to 10:00am
70%
100%
100%
On
10:00am to 11:00am
70%
100%
100%
On
11:00am to 12:00pm
70%
100%
100%
On
12:00pm to 1:00pm
70%
100%
100%
On
1:00pm to 2:00pm
70%
100%
100%
On
2:00pm to 3:00pm
70%
100%
100%
On
3:00pm to 4:00pm
70%
100%
100%
On
4:00pm to 5:00pm
70%
100%
100%
On
5:00pm to 6:00pm
35%
80%
80%
On
6:00pm to 7:00pm
10%
60%
65%
Off
7:00pm to 8:00pm
5%
60%
55%
Off
8:00pm to 9:00pm
5%
50%
25%
Off
9:00pm to 10:00pm
0%
15%
25%
Off
10:00pm to 11:00pm
0%
15%
25%
Off
11:00pm to 12:00am
0%
15%
25%
Off
Table Notes
The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building.
The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J7.
The appliances and equipment profile is expressed as a percentage of the maximum internal heat gain in Table S35C2I.
The air-conditioning profile is expressed as the plant status.
Table S35C2d Weekend occupancy and operation profiles of a Class 5 building, a Class 7 warehouse, a Class 8 Laboratory or a Class 9a clinic, day surgery or procedure unit
Time period (local standard time)
Occupancy (Saturday, Sunday and holidays)
Artificial lighting (Saturday, Sunday and holidays)
Appliances and equipment (Saturday, Sunday and holidays)
Air-conditioning (Saturday, Sunday and holidays)
12:00am to 1:00am
0%
15%
25%
Off
1:00am to 2:00am
0%
15%
25%
Off
2:00am to 3:00am
0%
15%
25%
Off
3:00am to 4:00am
0%
15%
25%
Off
4:00am to 5:00am
0%
15%
25%
Off
5:00am to 6:00am
0%
15%
25%
Off
6:00am to 7:00am
0%
15%
25%
Off
7:00am to 8:00am
0%
15%
25%
Off
8:00am to 9:00am
5%
25%
25%
Off
9:00am to 10:00am
5%
25%
25%
Off
10:00am to 11:00am
5%
25%
25%
Off
11:00am to 12:00pm
5%
25%
25%
Off
12:00pm to 1:00pm
5%
25%
25%
Off
1:00pm to 2:00pm
5%
25%
25%
Off
2:00pm to 3:00pm
5%
25%
25%
Off
3:00pm to 4:00pm
5%
25%
25%
Off
4:00pm to 5:00pm
5%
25%
25%
Off
5:00pm to 6:00pm
0%
15%
25%
Off
6:00pm to 7:00pm
0%
15%
25%
Off
7:00pm to 8:00pm
0%
15%
25%
Off
8:00pm to 9:00pm
0%
15%
25%
Off
9:00pm to 10:00pm
0%
15%
25%
Off
10:00pm to 11:00pm
0%
15%
25%
Off
11:00pm to 12:00am
0%
15%
25%
Off
Table Notes
The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building.
The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J7.
The appliances and equipment profile is expressed as a percentage of the maximum internal heat gain in Table S35C2l.
The air-conditioning profile is expressed as the plant status.
Table S35C2e Occupancy and operation profiles of a Class 6 shop or shopping centre
Time period (local standard time)
Occupancy (Daily)
Artificial lighting (Daily)
Appliances and equipment (Daily)
Air-conditioning (Daily)
12:00am to 1:00am
0%
25%
25%
Off
1:00am to 2:00am
0%
25%
25%
Off
2:00am to 3:00am
0%
25%
25%
Off
3:00am to 4:00am
0%
25%
25%
Off
4:00am to 5:00am
0%
25%
25%
Off
5:00am to 6:00am
0%
25%
25%
Off
6:00am to 7:00am
0%
25%
25%
Off
7:00am to 8:00am
10%
100%
70%
On
8:00am to 9:00am
20%
100%
70%
On
9:00am to 10:00am
20%
100%
70%
On
10:00am to 11:00am
15%
100%
70%
On
11:00am to 12:00pm
25%
100%
70%
On
12:00pm to 1:00pm
25%
100%
70%
On
1:00pm to 2:00pm
15%
100%
70%
On
2:00pm to 3:00pm
15%
100%
70%
On
3:00pm to 4:00pm
15%
100%
70%
On
4:00pm to 5:00pm
15%
100%
70%
On
5:00pm to 6:00pm
5%
100%
70%
On
6:00pm to 7:00pm
5%
100%
70%
Off
7:00pm to 8:00pm
0%
10%
10%
Off
8:00pm to 9:00pm
0%
10%
10%
Off
9:00pm to 10:00pm
0%
10%
10%
Off
10:00pm to 11:00pm
0%
10%
10%
Off
11:00pm to 12:00am
0%
10%
10%
Off
Table Notes
The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building.
The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J7.
The appliances and equipment profile is expressed as a percentage of the maximum internal heat gain in S35C2l.
The air-conditioning profile is expressed as the plant status.
Table S35C2f Occupancy and operation profiles of a Class 6 restaurant or cafe
Time period (local standard time)
O
Tables
- Table S35C2a Occupancy and operation profiles of a Class 2 common area
- Table S35C2b Occupancy and operation profiles of a Class 3 hotel
- Table S35C2c Weekday occupancy and operation profiles of a Class 5 building, a Class 7 warehouse, a Class 8 Laboratory or a Class 9a clinic, day surgery or procedure unit
- Table S35C2d Weekend occupancy and operation profiles of a Class 5 building, a Class 7 warehouse, a Class 8 Laboratory or a Class 9a clinic, day surgery or procedure unit
- Table S35C2e Occupancy and operation profiles of a Class 6 shop or shopping centre
- Table S35C2f Occupancy and operation profiles of a Class 6 restaurant or cafe
- Table S35C2g Occupancy and operation profiles of a Class 9a ward area
- Table S35C2h Occupancy and operation profiles of a Class 9b theatre or cinema
- Table S35C2i Occupancy and operation profiles of a Class 9b conference facility
- Table S35C2j Occupancy and operation profiles of a Class 9b school
- Table S35C2k Occupancy and operation profiles of a Class 9c aged care facility
- Table S35C2l Internal heat gains for appliances and equipment
- Table S35C2m Heated water supply consumption rates
- Table S35C2n Internal heat gains for occupants and hot meals
Changed in NCC 2025. See NCC 2025 Volume One S35C2, or show what changed.
(1) The air-conditioning, must be modelled on the basis of — the daily occupancy and operation profiles in Tables S35C2a, S35C2b, S35C2c, S35C2d, S35C2e, S35C2f, S35C2g, S35C2h, S35C2i, S35C2j and … lighting in the building with the daily profile in Tables S35C2a, S35C2b, S35C2c, S35C2d, S35C2e, S35C2f, S35C2g, S35C2h, S35C2i, S35C2j and … the basis of the consumption rates of Table S35C2m. Table S35C2a Occupancy and operation profiles of a Class 2 common area Time period (local standard time) Occupancy (Daily) Artificial lighting (Daily) Appliances and equipment (Daily) Air-conditioning (Daily) 12:00am to 1:00am 0% 30% 0% On 1:00am to 2:00am 0% 30% 0% On 2:00am to 3:00am 0% 30% 0% On 3:00am to 4:00am 0% 30% 0% On 4:00am to 5:00am 0% 30% 0% On 5:00am to 6:00am 0% 30% 0% On 6:00am to 7:00am 0% 50% 0% On 7:00am to 8:00am 0% 50% 0% On 8:00am to 9:00am 0% 50% 0% On 9:00am to 10:00am 0% 50% 0% On 10:00am to 11:00am 0% 50% 0% On 11:00am to 12:00pm 0% 50% 0% On 12:00pm to 1:00pm 0% 50% 0% On 1:00pm to 2:00pm 0% 50% 0% On 2:00pm to 3:00pm 0% 50% 0% On 3:00pm to 4:00pm 0% 50% 0% On 4:00pm to 5:00pm 0% 50% 0% On 5:00pm to 6:00pm 0% 50% 0% On 6:00pm to 7:00pm 0% 50% 0% On 7:00pm to 8:00pm 0% 50% 0% On 8:00pm to 9:00pm 0% 50% 0% On 9:00pm to 10:00pm 0% 50% 0% On 10:00pm to 11:00pm 0% 50% 0% On 11:00pm to 12:00am 0% 30% 0% On Table Notes The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J7. * * * * * This table reference has been deliberately left blank Table S35C2b Occupancy and operation profiles of a Class 3 … to Friday) Air-conditioning (Monday to Friday) 12:00am to 1:00am 0% 15% 0% 25% Off 1:00am to 2:00am 0% 15% 0% 25% Off 2:00am to 3:00am 0% 15% 0% 25% Off 3:00am to 4:00am 0% 15% 0% 25% Off 4:00am to 5:00am 0% 15% 0% 25% Off 5:00am to 6:00am 0% 15% 0% 25% Off 6:00am to 7:00am 0% 15% 0% 25% Off 7:00am to 8:00am 10% 40% 65% On 8:00am … to 9:00pm 5% 50% 25% Off 9:00pm to 10:00pm 0% 15% 0% 25% Off 10:00pm to 11:00pm 0% 15% 0% 25% Off 11:00pm to 12:00am 0% 15% 0% 25% Off Table Notes The occupancy profile is expressed as … a percentage of the maximum internal heat gain in Table S35C2I. S35C2l. The air-conditioning profile is expressed as the plant status. Table … holidays) Air-conditioning (Saturday, Sunday and holidays) 12:00am to 1:00am 0% 15% 0% 25% Off 1:00am to 2:00am 0% 15% 0% 25% Off 2:00am to 3:00am 0% 15% 0% 25% Off 3:00am to 4:00am 0% 15% 0% 25% Off 4:00am to 5:00am 0% 15% 0% 25% Off 5:00am to 6:00am 0% 15% 0% 25% Off 6:00am to 7:00am 0% 15% 0% 25% Off 7:00am to 8:00am 0% 15% 0% 25% Off 8:00am to 9:00am 5% 25% 15% 25% Off 9:00am to 10:00am 5% 25% 15% 25% Off 10:00am to 11:00am 5% 25% 15% 25% Off 11:00am to 12:00pm 5% 25% 15% 25% Off 12:00pm to 1:00pm 5% 25% 15% 25% Off 1:00pm to 2:00pm 5% 25% 15% 25% Off 2:00pm to 3:00pm 5% 25% 15% 25% Off 3:00pm to 4:00pm 5% 25% 15% 25% Off 4:00pm to 5:00pm 5% 25% 15% 25% Off 5:00pm to 6:00pm 0% 15% 0% 25% Off 6:00pm to 7:00pm 0% 15% 0% 25% Off 7:00pm to 8:00pm 0% 15% 0% 25% Off 8:00pm to 9:00pm 0% 15% 0% 25% Off 9:00pm to 10:00pm 0% 15% 0% 25% Off 10:00pm to 11:00pm 0% 15% 0% 25% Off 11:00pm to 12:00am 0% 15% 0% 25% Off Table Notes The occupancy profile is expressed as … Appliances and equipment (Daily) Air-conditioning (Daily) 12:00am to 1:00am 0% 25% 0% 25% Off 1:00am to 2:00am 0% 25% 0% 25% Off 2:00am to 3:00am 0% 25% 0% 25% Off 3:00am to 4:00am 0% 25% 0% 25% Off 4:00am to 5:00am 0% 25% 0% 25% Off 5:00am to 6:00am 0% 25% 0% 25% Off 6:00am to 7:00am 0% 25% 0% 25% Off 7:00am to 8:00am 10% 100% 70% On 8:00am … 12:00pm to 1:00pm 25% 100% 70% On 1:00pm to 2:00pm 15% 20% 100% 70% On 2:00pm to 3:00pm 15% 20% 100% 70% On 3:00pm to 4:00pm 15% 20% 100% 70% On 4:00pm to 5:00pm 15% 20% 100% 70% On 5:00pm to 6:00pm 5% 100% 70% On 6:00pm to 7:00pm 5% 100% 70% Off 7:00pm to 8:00pm 0% 10% 0% 10% Off 8:00pm to 9:00pm 0% 10% 0% 10% Off 9:00pm to 10:00pm 0% 10% 0% 10% Off 10:00pm to 11:00pm 0% 10% 0% 10% Off 11:00pm to 12:00am 0% 10% 0% 10% Off Table Notes The occupancy profile is expressed as … Class 6 restaurant or cafe Time period (local standard time) O Occupancy (Monday to Saturday) Artificial lighting (Monday to Saturday) Appliances and equipment (Monday to Saturday) Air-conditioning (Monday to Saturday) 12:00am to 1:00am 0% 5% 15% Off 1:00am to 2:00am 0% 5% 15% Off 2:00am to 3:00am 0% 5% 15% Off 3:00am to 4:00am 0% 5% 15% Off 4:00am to 5:00am 0% 5% 15% Off 5:00am to 6:00am 0% 5% 15% Off 6:00am to 7:00am 5% 40% 40% Off 7:00am to 8:00am 5% 40% 40% On 8:00am to 9:00am 5% 60% 60% On 9:00am to 10:00am 5% 60% 60% On 10:00am to 11:00am 20% 90% 90% On 11:00am to 12:00pm 50% 90% 90% On 12:00pm to 1:00pm 80% 90% 90% On 1:00pm to 2:00pm 70% 90% 90% On 2:00pm to 3:00pm 40% 90% 90% On 3:00pm to 4:00pm 20% 90% 90% On 4:00pm to 5:00pm 25% 90% 90% On 5:00pm to 6:00pm 50% 90% 90% On 6:00pm to 7:00pm 80% 90% 90% On 7:00pm to 8:00pm 80% 90% 90% On 8:00pm to 9:00pm 80% 90% 90% On 9:00pm to 10:00pm 50% 90% 90% On 10:00pm to 11:00pm 35% 50% 50% On 11:00pm to 12:00am 20% 30% 30% On Table Notes The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building. T
Removed words are struck through; added words are highlighted. Comparison of the text only.