Table S36C2h Typical R-Values for airspaces: non-reflective non-ventilated
Specification 36 Material properties
| Position of airspace | Direction of heat flow | R-Value |
|---|---|---|
| In a roof with a pitch not more than 5° or cathedral ceiling with a 20 mm to 50 mm thick roof airspace | Up | 0.15 |
| Down | 0.15 | |
| In a roof with a pitch not more than 5° or cathedral ceiling with a more than 50 mm to 300 mm thick roof airspace | Up | 0.15 |
| Down | 0.17 | |
| In a roof airspace greater than 300 mm thick or with a horizontal ceiling and a roof pitch more than 5° | Up | 0.18 |
| Down | 0.28 | |
| In a wall | Horizontal | 0.16 |
Table Notes
Linear interpolation may be used to calculate the R-Value of the airspace in a roof with an intermediate pitch.
A non-ventilated airspace in a roof is one with continuous cover, such as metal or sarked tiles, and no specific provision for ventilation.
R-Values are calculated using AS/NZS 4859.2 based on the following:
summer temperatures of 24°C internally and 36°C externally for heat transfer down; and
winter temperatures of 18°C internally and 12°C externally for heat transfer up; and
average of summer and winter results for horizontal heat transfer (e.g. in walls).
A non-ventilated airspace in a wall is one where there is no express provision for airflow through it and openings to the external environment do not exceed more than 500 mm2 per metre of length in the horizontal direction.
A non-ventilated airspace in a wall for the purposes of Note (4) includes a wall with drainage openings or weepholes that are open vertical joints in the outer leaf of a cavity masonry wall, which are not regarded as ventilation openings.
Table for S36C2 Construction Deemed-to-Satisfy