Table · NCC 2022 Volume One

Table S36C2h Typical R-Values for airspaces: non-reflective non-ventilated

Specification 36 Material properties

Open Table S36C2h on NCC Online ↗
Position of airspaceDirection of heat flowR-Value
In a roof with a pitch not more than 5° or cathedral ceiling with a 20 mm to 50 mm thick roof airspaceUp0.15
Down0.15
In a roof with a pitch not more than 5° or cathedral ceiling with a more than 50 mm to 300 mm thick roof airspaceUp0.15
Down0.17
In a roof airspace greater than 300 mm thick or with a horizontal ceiling and a roof pitch more than 5°Up0.18
Down0.28
In a wallHorizontal0.16

Table Notes

Linear interpolation may be used to calculate the R-Value of the airspace in a roof with an intermediate pitch.

A non-ventilated airspace in a roof is one with continuous cover, such as metal or sarked tiles, and no specific provision for ventilation.

R-Values are calculated using AS/NZS 4859.2 based on the following:

summer temperatures of 24°C internally and 36°C externally for heat transfer down; and

winter temperatures of 18°C internally and 12°C externally for heat transfer up; and

average of summer and winter results for horizontal heat transfer (e.g. in walls).

A non-ventilated airspace in a wall is one where there is no express provision for airflow through it and openings to the external environment do not exceed more than 500 mm2 per metre of length in the horizontal direction.

A non-ventilated airspace in a wall for the purposes of Note (4) includes a wall with drainage openings or weepholes that are open vertical joints in the outer leaf of a cavity masonry wall, which are not regarded as ventilation openings.

Table for S36C2 Construction Deemed-to-Satisfy

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S36C2h.