Table S36C2i Typical R-Values for airspaces: reflective non-ventilated

Specification 36 Material properties

Open Table S36C2i on NCC Online ↗
Position of airspaceDirection of heat flowR-Value
In a wall with an inner reflective surface of 0.05 emittance and a 20 mm to 100 mm airspace to the wall liningHorizontal0.61
In a wall with a central reflective membrane with an inner surface emittance of 0.05 and a 20 mm to 100 mm airspace from the membrane to the wall lining, and an outer anti-glare emittance of 0.08 and a 20 mm to 100 mm airspace to the wall claddingHorizontal1.1
In a wall with an outer anti-glare reflective surface of 0.08 emittance and a 20 mm to 100 mm airspace to the wall claddingHorizontal0.53

Table Notes

A non-ventilated airspace in a wall is one where there is no express provision for airflow through it and openings to the external environment do not exceed 500 mm2 per metre of length in the horizontal direction.

A non-ventilated airspace in a wall for the purposes of Note (1) includes a wall with drainage openings or weepholes that are open vertical joints in the outer leaf of a cavity masonry wall, which are not regarded as ventilation openings.

R-Values are calculated using AS/NZS 4859.2 based on the following:

summer temperatures of 24°C internally and 36°C externally for heat transfer down; and

winter temperatures of 18°C internally and 12°C externally for heat transfer up; and

average of summer and winter results for horizontal heat transfer (e.g. in walls); and

emittances are normal emittances of bounding surfaces in accordance with AS 4200.1.

Table for S36C2 Construction Deemed-to-Satisfy

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S36C2i.