Table S36C2i Typical R-Values for airspaces: reflective non-ventilated
Specification 36 Material properties
| Position of airspace | Direction of heat flow | R-Value |
|---|---|---|
| In a wall with an inner reflective surface of 0.05 emittance and a 20 mm to 100 mm airspace to the wall lining | Horizontal | 0.61 |
| In a wall with a central reflective membrane with an inner surface emittance of 0.05 and a 20 mm to 100 mm airspace from the membrane to the wall lining, and an outer anti-glare emittance of 0.08 and a 20 mm to 100 mm airspace to the wall cladding | Horizontal | 1.1 |
| In a wall with an outer anti-glare reflective surface of 0.08 emittance and a 20 mm to 100 mm airspace to the wall cladding | Horizontal | 0.53 |
Table Notes
A non-ventilated airspace in a wall is one where there is no express provision for airflow through it and openings to the external environment do not exceed 500 mm2 per metre of length in the horizontal direction.
A non-ventilated airspace in a wall for the purposes of Note (1) includes a wall with drainage openings or weepholes that are open vertical joints in the outer leaf of a cavity masonry wall, which are not regarded as ventilation openings.
R-Values are calculated using AS/NZS 4859.2 based on the following:
summer temperatures of 24°C internally and 36°C externally for heat transfer down; and
winter temperatures of 18°C internally and 12°C externally for heat transfer up; and
average of summer and winter results for horizontal heat transfer (e.g. in walls); and
emittances are normal emittances of bounding surfaces in accordance with AS 4200.1.