Table · NCC 2022 Volume One
Table S45C3d Internal heat loads for lighting, cooking and appliances
Specification 45 Modelling profiles for J1V5
| Sole-occupancy unit area (excluding garage) (m2) | Occupancy (m2/person) | Day time lighting power density (6:00 am to 6:00 pm) (W/m2) | Night-time lighting power density (6:00 pm to 6:00 am) (W/m2) | Cooking in kitchen zone only (W/m2 kitchen area) | Appliances (except oven) in whole sole-occupancy unit (W/m2) |
|---|---|---|---|---|---|
| ≤ 100 | 41.2 | 4.0 | 4.0 | 36.2 | 4.38 |
| > 100 to ≤ 125 | 44.3 | 4.0 | 4.0 | 34.7 | 3.52 |
| > 125 to ≤ 150 | 47.8 | 4.0 | 4.0 | 28.9 | 2.99 |
| > 150 to ≤ 175 | 51.7 | 4.0 | 4.0 | 24.8 | 2.60 |
| > 175 to ≤ 200 | 55.8 | 4.0 | 4.0 | 25.3 | 2.26 |
| > 200 to ≤ 225 | 60.0 | 4.0 | 4.0 | 22.5 | 2.02 |
| > 225 to ≤ 250 | 64.4 | 4.0 | 4.0 | 20.2 | 1.84 |
| > 250 to ≤ 275 | 68.9 | 4.0 | 4.0 | 18.4 | 1.68 |
| > 275 to ≤ 300 | 73.3 | 4.0 | 4.0 | 16.9 | 1.55 |
| > 300 to ≤ 325 | 77.5 | 4.0 | 4.0 | 15.6 | 1.44 |
| > 325 to ≤ 350 | 81.6 | 4.0 | 4.0 | 14.5 | 1.34 |
| > 350 to ≤ 375 | 85.4 | 4.0 | 4.0 | 13.5 | 1.26 |
| > 375 | 89.0 | 4.0 | 4.0 | 12.7 | 1.19 |
Table for S45C3 Proposed building and reference building
Not in NCC 2025. No Table S45C3d in NCC 2025 Volume One.