Specification clause · NCC 2022 Volume One

S45C3 Proposed building and reference building

Specification 45 Modelling profiles for J1V5

Open S45C3 on NCC Online ↗

(1) The heating load, cooling load and energy value for J1V5(1) and (2) must be calculated for both the proposed building and the reference building sole-occupancy unit using the same—

heating load or cooling load limits, calculated using heating degree hours, cooling degree hours and dehumidification gram hours from Table S45C3a; and

energy value factors from Tables S45C3b and S45C3c; and

location, in accordance with S34C3(3); and

climatic data, using the Typical Meteorological Year weather files drawn from the years 1990 to 2015 published by CSIRO; and

adjacent structures and features; and

orientation; and

building form, including—

roof geometry; and

floor plan; and

number of storeys; and

location, extent and configuration of ground floors and basements; and

the size and location of glazing; and

external doors; and

walls between or bounding sole-occupancy units; and

balconies; and

testing standards, including for insulation, glazing, water heater and unitary air-conditioning equipment; and

fabric and glazing, including—

thermal resistance of air films including any adjustment factors, moisture content of materials and the like; and

internal shading devices, including their colour and criteria for operation; and

system configuration and control of air-conditioning services and energy sources other than renewable energy generated on-site where present; and

capacity and water usage, for on-site domestic heated water systems, assuming—

a consumption rate in accordance with Table A.6.2 of AS/NZS 4234 of 10 L plus 1.25 L per m2 of floor area per sole-occupancy unit per day; and

a seasonal load profile in accordance with Table A.6.3 of AS/NZS 4234; and

a water inlet temperature of the monthly ground temperature in accordance with Table A.8 of AS/NZS 4234; and

a water outlet temperature of 60°C; and

the same calculation method for standing losses; and

internal heating loads, in accordance with Table S45C3d; and

occupancy profiles, in accordance with Tables S45C3e, S45C3f, S45C3g, S45C3h, S45C3i, S45C3j, S45C3k and S45C3l; and

internal zoning, assuming—

daytime air-conditioned zones include at least one living space and one dining space; and

kitchen zones are a separate zone using virtual wall partitions at all times, and are only air-conditioned if adjacent to an external façade; and

each bedroom is a night-time air-conditioned zone; and

all other zones, including pantries, corridors, en-suites, walk-in robes, bathrooms, toilets, laundries and adjacent roof space or basement are unconditioned; and

the same assumptions and means of calculating the temperature difference across air-conditioning zone boundaries; and

the same floor coverings, furniture and fittings density; and

the same internal artificial lighting illumination levels.

(2) Where present, the air-conditioning services, including all centralised domestic services infrastructure, of each sole-occupancy unit of both the proposed building and the reference building must be modelled with—

in climate zone 2 to 8, a heating thermostat setting of—

20°C for all conditioned zones from 6:00 am to 12:00 am; and

18°C at all other times; and

a cooling thermostat setting of—

in climate zones 1, 2 and 3, 27°C for all daytime conditioned zones from 6:00 am to 11:00 pm; and

in climate zone 4, 26°C for all daytime conditioned zones from 6:00 am to 11:00 pm; and

in climate zone 5, 25°C for all daytime conditioned zones from 6:00 am to 11:00 pm; and

in climate zones 6 and 7, 24°C for all daytime conditioned from 6:00 am to 11:00pm; and

in climate zone 8, 23°C for all daytime conditioned zones from 6:00 am to 11:00 pm; and

in all climate zones, a constant cooling thermostat setting of 24°C for all night-time conditioned zones.

(3) Natural ventilation of each sole-occupancy unit of the proposed building and the reference building must be modelled with the same—

frequency of data output, being at least hourly; and

opening flow properties in accordance with Table S45C3m; and

wind pressure coefficients in accordance with Tables S45C3n and S45C3o; and

infiltration values, unless building sealing is verified using J1V4, in which case infiltration values equal to the intended building air change rate at 50 Pa divided by 20 may be used for the proposed building only; and

operation settings as follows:

openings must shut when the external dry bulb temperature is less than or equal to a temperature 1°C higher than the air-conditioning service cooling set point; and

openings must shut when the external dry bulb temperature is greater than or equal to a temperature 1°C lower than the air-conditioning service heating set point; and

openings must remain open for all hours of the year that do not meet the above closing conditions.

Table S45C3a Annual heating degree hours, cooling degree hours and dehumidification gram hours for various locations

Climate zone

Location

Annual heating degree hours

Annual cooling degree hours

Annual dehumidification gram hours

1

Darwin

0

15770

15364

1

Port Hedland

859

16540

8011

1

Townsville

595

6392

5843

1

Weipa

4

12144

12565

1

Wyndham

126

26975

9184

1

Willis Island

N/A

N/A

N/A

1

Cairns

268

6411

6030

1

Broome

624

14749

14083

2

Rockhampton

3283

6717

1701

2

Amberley

10958

4483

290

2

Brisbane

4744

2228

1415

2

Coffs Harbour

7137

1309

231

2

Mackay

976

3183

5214

2

Gladstone

568

4307

3543

2

Oakey

15392

3979

40

3

Longreach

6002

14634

505

3

Carnarvon

2260

4810

1023

3

Alice Springs

11767

13149

125

3

Charleville

11284

9580

230

3

Halls Creek

611

19571

2109

3

Tennant Creek

1171

18644

1747

3

Mount Isa

3060

15813

1797

3

Newman

6286

15240

645

4

Moree

13986

7291

151

4

Wagga

24833

4678

0

4

Mildura

19003

6300

11

4

Meekatharra

6883

12766

67

4

Oodnadatta

8352

13845

18

4

Kalgoorlie

13048

7763

31

4

Woomera

11754

8434

3

4

Cobar

13663

7616

101

4

Dubbo

20431

5332

36

4

Giles

6259

13082

81

5

Geraldton

6846

6365

10

5

Perth

11024

6084

0

5

Williamtown

11713

2802

276

5

Adelaide

13066

5132

0

5

Sydney RO (Observatory Hill)

7079

1466

129

5

Bickley

15664

4015

34

5

Swanbourne

6322

3332

63

5

Ceduna

14061

5212

53

5

Mandurah

6081

3131

2

5

Esperance

11009

1884

0

5

Manjimup

20910

2531

0

5

Mascot (Sydney Airport)

6357

1596

110

6

Nowra

14813

2801

56

6

Melbourne RO

14494

2416

0

6

East Sale

27229

1259

0

6

Katanning

21496

3566

14

6

Forrest

15294

8410

14

6

Albany

16131

932

0

6

Mount Lofty

41095

1626

0

6

Tullamarine (Melbourne Airport)

23496

2764

0

6

Mount Gambier

28496

2764

0

6

Moorabbin

20249

2291

0

6

Warnambool

27285

1406

1

6

Cape Otway

19279

960

3

6

Richmond

15607

3917

60

7

Armidale

33374

1039

9

7

Launceston (Ti Tree Bend)

30952

833

0

7

Canberra

35153

2863

0

7

Cabramurra

65831

79

0

7

Hobart

28542

451

0

7

Orange

40325

1192

2

7

Ballarat

37873

2585

2

7

Low Head

26047

80

0

7

Launceston Airport

39444

456

0

7

Learmonth

1646

14048

958

8

Thredbo (Village)

61209

147

0

Table Notes

If location is not listed, use the nearest appropriate.

Table S45C3b Energy factors based on fuel type

Fuel type

ACT

NSW

NT

Qld

SA

Tas

Vic

WA

Electricity: peak (kWh)

1.55

1.53

1.54

1.53

1.54

1.55

1.53

1.54

Electricity: shoulder (kWh)

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

Electricity: off-peak (kWh)

0.78

0.79

0.79

0.79

0.78

0.78

0.79

0.79

Electricity: cont. load (kWh)

0.68

0.54

1.11

0.76

0.62

0.70

0.82

0.47

Natural gas (MJ)

0.18

0.14

0.16

0.24

0.13

0.21

0.10

0.16

Electricity: PV export (kWh)

0.42

0.39

1.10

0.51

0.35

0.50

0.53

0.29

Table S45C3c Electricity usage — timing for categories of usage

Hour

Hour span

Weekday

1

24-1

Off-peak

2

1-2

Off-peak

3

2-3

Off-peak

4

3-4

Off-peak

5

4-5

Off-peak

6

5-6

Off-peak

7

6-7

Off-peak

8

7-8

Peak

9

8-9

Peak

10

9-10

Shoulder

11

10-11

Shoulder

12

11-12

Shoulder

13

12-13

Shoulder

14

13-14

Shoulder

15

14-15

Shoulder

16

15-16

Shoulder

17

16-17

Peak

18

17-18

Peak

19

18-19

Peak

20

19-20

Peak

21

20-21

Shoulder

22

21-22

Shoulder

23

22-23

Off-peak

24

23-24

Off-peak

Table S45C3d Internal heat loads for lighting, cooking and appliances

Sole-occupancy unit area (excluding garage) (m2)

Occupancy (m2/person)

Day time lighting power density (6:00 am to 6:0

Tables