Table · NCC 2022 Volume One
Table S5C21a Type B construction: FRL of loadbearing parts of external walls
Specification 5 Fire-resisting construction
| Distance from a fire-source feature | FRL (in minutes) Structural adequacy / Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Less than 1.5 m | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 |
| 1.5 to less than 3 m | 90/60/30 | 120/90/60 | 180/120/90 | 240/180/120 |
| 3 m to less than 9 m | 90/30/30 | 120/30/30 | 180/90/60 | 240/90/60 |
| 9 m to less than 18 m | 90/30/– | 120/30/– | 180/60/– | 240/60/– |
| 18 m or more | –/–/– | –/–/– | –/–/– | –/–/– |
Table for S5C21 Type B fire-resisting construction — fire-resistance of building elements
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C21a.