Table S5C21a Type B construction: FRL of loadbearing parts of external walls

Specification 5 Fire-resisting construction

Open Table S5C21a on NCC Online ↗
Distance from a fire-source featureFRL (in minutes) Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 partClass 5, 7a or 9Class 6Class 7b or 8
Less than 1.5 m90/90/90120/120/120180/180/180240/240/240
1.5 to less than 3 m90/60/30120/90/60180/120/90240/180/120
3 m to less than 9 m90/30/30120/30/30180/90/60240/90/60
9 m to less than 18 m90/30/–120/30/–180/60/–240/60/–
18 m or more–/–/––/–/––/–/––/–/–

Table for S5C21 Type B fire-resisting construction — fire-resistance of building elements

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S5C21a.

Defined terms used