Table S5C21g Type B construction: FRL of other building elements not covered by Tables S5C21a to S5C21f

Specification 5 Fire-resisting construction

Open Table S5C21g on NCC Online ↗
Building elementFRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 partClass 5, 7a or 9Class 6Class 7b or 8
Other loadbearing internal walls and columns60/–/–120/–/–180/–/–240/–/–
Roofs–/–/––/–/––/–/––/–/–

Table for S5C21 Type B fire-resisting construction — fire-resistance of building elements