Table · NCC 2022 Volume One

Table S5C21f Type B construction: FRL of non-loadbearing internal walls

Specification 5 Fire-resisting construction

Open Table S5C21f on NCC Online ↗
LocationFRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 partClass 5, 7a or 9Class 6Class 7b or 8
Fire-resisting lift and stair shafts–/90/90–/120/120–/120/120–/120/120
Bounding public corridor, public lobbies and the like–/60/60–/–/––/–/––/–/–
Between or bounding sole-occupancy units–/60/60–/–/––/–/––/–/–

Table for S5C21 Type B fire-resisting construction — fire-resistance of building elements

Changed in NCC 2025 (minor wording). See NCC 2025 Volume One Table S5C21f, or show what changed.

Location | FRL (in minutes): Structural adequacy / Integrity / … 9 | Class 6 | Class 7b or 8 Fire-resisting lift and stair shafts | –/90/90 | –/120/120 | –/120/120 | –/120/120 … sole-occupancy units | –/60/60 | –/–/– | –/–/– | –/–/–

Removed words are struck through; added words are highlighted. Comparison of the text only.