Table · NCC 2022 Volume One
Table S7C2 Fire hazard property requirements
Specification 7 Fire hazard properties
| Lining, material or assembly | Requirement |
|---|---|
| Floor linings and floor coverings | S7C3 |
| Wall linings and ceiling linings | S7C4 |
| Air-handling ductwork | S7C5 |
| Lift cars | S7C6 |
| In fire control rooms subject to Specification 6 and fire isolated exits | S7C7 |
| In Class 9b buildings used as a theatre, public hall or the like — fixed seating in the audience area or auditorium; and a proscenium curtain required by Specification 32 | S7C7 |
| Escalators, moving walkways and non-required non-fire-isolated stairways or pedestrian ramps subject to Specification 14 | S7C7 |
| Sarking-type material | S7C7 |
| Attachments to internal floors, walls and ceilings | S7C7 |
| Other materials including insulation | S7C7 |
Table for S7C2 Application
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S7C2.
Clauses referred to
- S7C3 Floor linings and floor coverings
- S7C4 Wall and ceiling linings
- S7C5 Air-handling ductwork
- S7C6 Lift cars
- S7C7 Other materials