Specification clause · NCC 2022 Volume One

S7C3 Floor linings and floor coverings

Specification 7 Fire hazard properties · NCC 2019: Spec C1.10: 3

Open S7C3 on NCC Online ↗

A floor lining or floor covering must have—

a critical radiant flux not less than that listed in Table S7C3; and

in a building not protected by a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17, a maximum smoke development rate of 750 percent-minutes; and

a group number complying with S7C6(b), for any portion of the floor covering that is continued more than 150 mm up a wall.

Table S7C3 Critical radiant flux (CHF in kW/m2) of floor linings and floor coverings

Class of building

Building not fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17

Building fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17

Fire-isolated exits and fire control rooms

Class 2, 3, 5, 6, 7, 8 or 9b, excluding Class 3 accommodation for the aged and Class 9b as specified below

2.2 kW/m2

1.2 kW/m2

2.2 kW/m2

Class 3 accommodation for the aged

4.5 kW/m2

2.2 kW/m2

4.5 kW/m2

Class 9a patient care areas

4.5 kW/m2

2.2 kW/m2

4.5 kW/m2

Class 9a areas other than patient care areas

2.2 kW/m2

1.2 kW/m2

4.5 kW/m2

Class 9b auditorium or audience seating area used mainly for indoor swimming or ice skating

1.2 kW/m2

1.2 kW/m2

2.2 kW/m2

Class 9b auditorium or audience seating area used mainly for other sports or multi-purpose functions

2.2 kW/m2

1.2 kW/m2

2.2 kW/m2

Class 9c resident use area

N/A

2.2 kW/m2

4.5 kW/m2

Class 9c areas other than resident use areas

N/A

1.2 kW/m2

4.5 kW/m2

Tables

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S7C3.