Table · NCC 2022 Volume One

Table S7C4 Wall and ceiling lining materials (material groups permitted)

Specification 7 Fire hazard properties

Open Table S7C4 on NCC Online ↗
Class of buildingFire-isolated exits and fire control roomsPublic corridorsSpecific areasOther areas
Class 2 or 3, unsprinklered, excluding accommodation for the aged, people with disabilities and childrenWalls: 1Walls: 1, 2Walls: 1, 2, 3Walls: 1, 2, 3
Ceilings: 1Ceilings: 1, 2Ceilings: 1, 2, 3Ceilings: 1, 2, 3
Class 2 or 3, sprinklered, excluding accommodation for the aged, people with disabilities and childrenWalls: 1Walls: 1, 2, 3Walls: 1, 2, 3Walls: 1, 2, 3
Ceilings: 1Ceilings: 1, 2, 3Ceilings: 1, 2, 3Ceilings: 1, 2, 3
Class 3 or 9a, unsprinklered, accommodation for the aged, people with a disability, children and health-care buildingsWalls: 1Walls: 1Walls: 1, 2Walls: 1, 2, 3
Ceilings: 1Ceilings: 1Ceilings: 1, 2Ceilings: 1, 2, 3
Class 3 or 9a, sprinklered, accommodation for the aged, people with a disability, children and health-care buildingsWalls: 1Walls: 1, 2Walls: 1, 2, 3Walls: 1, 2, 3
Ceilings: 1Ceilings: 1, 2Ceilings: 1, 2, 3Ceilings: 1, 2, 3
Class 5, 6, 7, 8 or 9b schools, unsprinkleredWalls: 1Walls: 1, 2Walls: 1, 2, 3Walls: 1, 2, 3
Ceilings: 1Ceilings: 1, 2Ceilings: 1, 2Ceilings: 1, 2, 3
Class 5, 6, 7, 8 or 9b schools, sprinkleredWalls: 1Walls: 1, 2, 3Walls: 1, 2, 3Walls: 1, 2, 3
Ceilings: 1Ceilings: 1, 2, 3Ceilings: 1, 2, 3Ceilings: 1 ,2, 3
Class 9b other than schools, unsprinkleredWalls: 1Walls: 1Walls: 1, 2Walls: 1, 2, 3
Ceilings: 1Ceilings: 1Ceilings: 1, 2Ceilings: 1, 2, 3
Class 9b other than schools, sprinkleredWalls: 1Walls: 1, 2Walls: 1, 2, 3Walls: 1, 2, 3
Ceilings: 1Ceilings: 1, 2Ceilings: 1, 2, 3Ceilings: 1, 2, 3
Class 9c, sprinkleredWalls: 1Walls: 1, 2Walls: 1, 2, 3Walls: 1, 2, 3
Ceilings: 1Ceilings: 1, 2Ceilings: 1, 2, 3Ceilings: 1, 2, 3

Table Notes

”Sprinklered” means a building fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

”Specific areas” means within—

for Class 2 and 3 buildings, a sole-occupancy unit; and

for Class 5 buildings, open plan offices with a minimum floor dimension/floor to ceiling height ratio > 5; and

for Class 6 buildings, shops or other building with a minimum floor dimension/floor to ceiling height ratio > 5; and

for Class 9a health-care buildings, patient care areas; and

for Class 9b theatres and halls, etc, an auditorium; and

for Class 9b schools, a classroom; and

for Class 9c buildings, resident use area.

Table for S7C4 Wall and ceiling linings