Tasmania variation · NCC 2022 Volume One

TAS E1P7 Automatic fire detection system

Part E1 Fire fighting equipment

Open on NCC Online ↗

Insert TAS clause E1P7 in clause E1P7 as follows:

An automatic fire detection system must be installed to the degree necessary to alert the fire brigade of fire so that fire fighting operations may be undertaken at the earliest possible time to limit property and environmental damage appropriate to—

the building functions and use; and

the fire hazard; and

the height of the building; and

the building floor area.

Applications

Tas E1P7 only applies to—

a Class 5 building or Class 6 building having an aggregate floor area of more than 1000 m2; and

a Class 7 building having a floor area of more than 1000 m2 in which furniture is stored; and

a Class 8 building which is a special fire hazard building and in which more than 25 persons are employed; and

a Class 9b building which is a school or early childhood centre or a creche which—

is of more than 1 storey; or

has a storey with a floor area more than 500 m2; and

a Class 9b building which is a theatre.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One TAS E1P7.