Tasmania variation · NCC 2022 Volume One

TAS I12D4 Maximum floor areas

TAS Part I12 Premises for manufacture or processing of glass reinforced plastics

Open on NCC Online ↗

The floor area of any building or fire-separated section must not exceed the relevant maximum floor area set out in Table TAS I12D4.

Insert TAS table (I12D4) I12D4 as follows:

TAS Table I12D4: Maximum floor area of buildings for manufacture or processing of glass reinforced plastics or isocyanates

Type A building construction

Type B building construction

Type C building construction

Not sprinklered: 1500 m2

Not sprinklered: 1200 m2

Not sprinklered: 1000 m2

Sprinklered: 6000 m2

Sprinklered: 5000 m2

Sprinklered: 3000 m2