TAS I12D7 Ventilation
TAS Part I12 Premises for manufacture or processing of glass reinforced plastics
(1) Mechanical or natural ventilation must be via low-level, exhaust ducting in a wall and a fixed, open, floor-level, fresh-air inlet ducting in the opposite wall such as to ensure a cross flow of the ventilation over the complete working area.
(2) Mechanical ventilation must provide not less than 6 air changes per hour.
(3) The ventilation fan and exhaust ducting must be arranged in such a manner as to—
produce a negative pressure within any exhaust ducting within the work place so that a leak in the ducting will not vent exhaust air back in to the work place; and
vent the exhaust air to the atmosphere so as to prevent recirculation of that exhaust air.