Tasmania variation · NCC 2022 Volume One

TAS I13D7 Bulk stores for polyols and isocyanates

TAS Part I13 Premises for production of processing of isocyanates

Open on NCC Online ↗

(1) A bulk store for polyols must be constructed from non-combustible materials and have a smooth impervious concrete floor and it must protect the polyols from direct exposure to the sun’s radiation.

(2) A bulk store for isocyanates must—

be constructed from non-combustible materials, have a smooth impervious concrete floor, and must protect the isocyanate containers from direct exposure to the sun; and

if it is used for the storage of either TDI or HDI and is not an open sided building, be fitted with mechanical ventilation so that the TLV is not exceeded at any time provided that the ventilation must provide not less than 6 air changes per hour.

(3) The area around both a polyol bulk store and an isocyanate bulk store must be bunded, the bund or bunds must ensure separation of the polyol and isocyanate areas and each bund must have a capacity of 10% more than the storage capacity of the largest tank it protects.

Changed in NCC 2025. See NCC 2025 Volume One TAS I13D7, or show what changed.

Delete clause I13D7 and insert TAS I13D7 as follows: (1) A bulk store for polyols must be constructed from … than the storage capacity of the largest tank it protects.

Removed words are struck through; added words are highlighted. Comparison of the text only.