Tasmania variation · NCC 2022 Volume One
TAS I14D3 Height of plating area
TAS Part I14 Premises for electro-plating, electro-polishing, anodising or etching
Every part of a plating area must be not less than 2.7 m in height—
measured from the floor to the ceiling if a ceiling is provided; or
measured from the floor to the lowest part of the roof if a ceiling is not provided.
Changed in NCC 2025. See NCC 2025 Volume One TAS I14D3, or show what changed.
Delete clause I14D3 and insert TAS I14D3 as follows: Every part of a plating area must be not less … part of the roof if a ceiling is not provided.
Removed words are struck through; added words are highlighted. Comparison of the text only.