TAS I4D3 General requirements
TAS Part I4 Food premises
(1) The provision of—
close-fitting windows and doors; and
air intakes that do not draw in contaminated air; and
air locks and self-closing doors to separate toilet areas, laundries and living areas from food handling areas; and
mechanical ventilation that removes sources of contamination,
satisfies TAS I4P2(d)(i).
(2) The provision of—
self-closing or pest-screened external doors; and
mesh screens at opening windows or other ventilation openings; and
sealing to drains, grease traps and ventilation pipes; and
sealing to openings where pipes pass through external walls; and
the installation of pest-proof flashings to doors,
satisfies TAS I4P2(d)(ii).
(3) The provision of—
vermin-proof sealing; or
filling; or
access for inspection and cleaning of boxed-in areas,
satisfies TAS I4P2(d)(iii).
(4) The provision of a reticulated water supply from—
a regulated entity; or
a private water supply with on-site treatment,
which meets the Australian Drinking Water Guidelines, satisfies TAS I4P3(2).
Notes
‘Regulated entity’ has the same meaning as Water and Sewerage Industry Act 2008.
Changed in NCC 2025. See NCC 2025 Volume One TAS I4D3, or show what changed.
Delete clause I4D3 and insert TAS I4D3 as follows: (1) The provision of — close-fitting windows and doors; and … the same meaning as Water and Sewerage Industry Act 2008.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Other states and territories
- VIC The clear width of all bedroom entrance doorways must be not less than 900 mm. (2) The clear width of all other…
- WA In a WA public buildings, each storey that accommodates more than 50 persons must have more than one exit from that…
- NSW Where an entertainment venue is used principally for the purpose of— exhibiting films; or conducting live stage…