VIC G5F1 Construction in bushfire prone areas
Part G5 Construction in bushfire prone areas · varies G5F1 Construction in bushfire prone areas
Delete clause G5F1 and insert VIC G5F1 as follows:
A building constructed in a designated bushfire prone area—
is to provide a resistance to bushfires in order to reduce the danger to life and minimise the risk of the loss of the building; and
if occupied by people who may be unable to readily evacuate the building prior to a bushfire, is to be constructed so as to provide its occupants shelter from the direct and indirect actions of a bushfire.
Applications
VIC G5F1(a) apply in a designated bushfire prone area to—
a Class 2 or 3 building; or
a Class 10a building or deck associated with a Class 2 or 3 building; or
a Class 10a building or deck immediately adjacent or connected to a building of a type listed in (2)(a), (b) or (c).
VIC G5F1(a) and (b) apply in a designated bushfire prone area to—
a Class 9a health-care building; and
a Class 9b—
early childhood centre; and
primary or secondary school; and
a Class 9c residential care building; and
a Class 4 part of a building associated with a building of a type listed in (a) to (c).