Western Australia variation · NCC 2022 Volume One
WA I4D4 Goings and risers
WA Part I4 Public buildings
(1) Steps serving a WA public building must have risers not more than 180 mm and goings not less than 280 mm.
(2) The requirements of (1) do not apply to steps in a fire-isolated stairway.
Changed in NCC 2025. See NCC 2025 Volume One WA I4D4, or show what changed.
Delete clause I4D4 and insert WA I4D4 as follows: (1) Steps serving a WA public building must have risers … (1) do not apply to steps in a fire-isolated stairway.
Removed words are struck through; added words are highlighted. Comparison of the text only.