Performance Requirement · NCC 2022 Volume Three

B2P9 Pressure

Part B2 Heated water services · NCC 2019: BP2.3, TAS Exemption 1

Open B2P9 on NCC Online ↗
Varied in TAS. Check the variation for your state.

The points of discharge for a heated water service must—

have—

a working pressure of not less than 50 kPa; and

a static pressure within the building of not more than 500 kPa; or

have water pressures suitable for the correct functioning of the fixture or appliance where water pressures are outside of (a)(i) and (a)(ii) are required.

Changed in NCC 2025. See NCC 2025 Volume Three B2P9, or show what changed.

The points of discharge for Heated water from a heated water service must — have — a working pressure of not less than 50 kPa; and a static pressure within the building of not more than 500 kPa; or have water pressures suitable be provided at appropriate temperatures for the correct functioning of the fixture fixtures or appliance where water pressures are outside of (a)(i) and (a)(ii) are required. appliances.