Performance Requirement · NCC 2025 Volume Three

B2P9 Temperature

Part B2 Heated water services · NCC 2019: BP2.3, TAS Exemption 1

Open B2P9 on NCC Online ↗

Heated water from a heated water service must be provided at appropriate temperatures for the correct functioning of fixtures or appliances.

Changed since NCC 2022. See NCC 2022 Volume Three B2P9, or show what changed.

The points of discharge for Heated water from a heated water service must — have — a working pressure of not less than 50 kPa; and a static pressure within the building of not more than 500 kPa; or have water pressures suitable be provided at appropriate temperatures for the correct functioning of the fixture fixtures or appliance where water pressures are outside of (a)(i) and (a)(ii) are required. appliances.

Removed words are struck through; added words are highlighted. Comparison of the text only.