B4D3 Fire sprinkler systems
Part B4 Fire-fighting water services
(1) Automatic fire sprinkler systems must be in accordance with—
AS 2118.1 for general systems; or
AS 2118.4 for accommodation buildings not exceeding four stories; or
AS 2118.5 for home fire sprinkler systems.
(2) Automatic fire sprinkler systems for combined sprinkler and hydrant systems in multi-storey buildings must be in accordance with—
AS 2118.1 for general systems; or
AS 2118.6 for multi-storey buildings; or
FPAA101H for buildings which are less than 25m in effective height and contain Class 2 and Class 3 parts.
Changed in NCC 2025. See NCC 2025 Volume Three B4D3, or show what changed.
(1) Automatic fire sprinkler systems must be in accordance with … systems; or AS 2118.4 for accommodation buildings not exceeding four stories; storeys; or AS 2118.5 for home fire sprinkler systems. (2) Automatic … effective height and contain Class 2 and Class 3 parts. (3) Notwithstanding (2)(b), plastic pipes and fittings must not be used above-ground in combined sprinkler and hydrant systems.
Removed words are struck through; added words are highlighted. Comparison of the text only.