B5D3 Non-drinking water service
Part B5 Cross-connection control · NCC 2019: B5.3
(1) A hazard exists wherever it is possible for water or contaminants to enter a non-drinking water service or supply via any potential cross-connection between itself and another separate non-drinking water service on the same site.
(2) Each hazard must—
be assigned a Containment protection Hazard Rating in accordance with S41C6; and
be isolated from the non-drinking water service by appropriate containment protection which is selected and installed in accordance with Section 4 of AS/NZS 3500.1.
Changed in NCC 2025. See NCC 2025 Volume Three B5D3, or show what changed.
(1) A hazard exists wherever it is possible for water or contaminants to enter a non-drinking water service or supply via any potential or actual cross-connection between itself and another separate non-drinking water service on the same site. (2) Each hazard must — be assigned a Containment protection Hazard Rating in accordance with S41C6; B5D7(10), B5D7(11) or B5D7(12); and be isolated from the non-drinking water service by appropriate containment protection which is selected and installed in accordance with Section 4 of AS/NZS 3500.1. Exemptions B5D3 is not applicable to non-drinking water service used for agricultural purposes where the non-drinking water service is supplied solely by non-drinking water service(s) and is fully independent from any other water service.