NSW B5D6 Rainwater
Part B5 Cross-connection control · varies B5D6 Rainwater
Delete clause B5D6 and insert NSW B5D6 as follows:
Drinking water and non-drinking water must:
be zone protected from above ground, buried or partially buried rainwater tank in Class 1 buildings, utilising a non-testable device; or
comply with AS/NZS 3500.1 (2018) Clause 16.4 and Table 16.4 for all other building classes.
Applications
B5D6 applies to scenarios not covered by S41C6(1)(b).
Changed in NCC 2025. See NCC 2025 Volume Three NSW B5D6, or show what changed.
Delete clause B5D6 and insert NSW B5D6 as follows: Drinking When drinking water is used to top up a rainwater tank or supplement a rainwater service through the use of changeover device: it must be assigned a hazard rating based on the following building and non-drinking water must: be rainwater tank types: zone protected from above ground, buried or partially buried rainwater tank in Class 1 buildings, utilising using a non-testable low hazard device; or comply with AS/NZS 3500.1 (2018) Clause 16.4 and Table 16.4 zone protected for all other building classes. Applications B5D6 applies classes of buildings using: High hazard device for buried rainwater tanks, Low Hazard for partially buried rainwater tanks, and Low Hazard for above ground rainwater tanks devices are to scenarios not covered by S41C6(1)(b). be selected and installed in accordance with Section 4 of AS/NZS 3500.1:
Removed words are struck through; added words are highlighted. Comparison of the text only.