SA B5D6 Rainwater
Part B5 Cross-connection control · varies B5D6 Rainwater
Delete clause B5D6 and insert SA B5D6 as follows:
Protection of drinking water services from rainwater must be in accordance with AS/NZS 3500.1(2018) Clause 16.4 and Table 16.4 with the additions;
After 16.4, insert clause 16.4.1 as follows: 16.4.1 A reduction of the Hazard Rating listed in table 16.4 may be permitted following a risk assessment of the design and installation of the rainwater tank and other environmental factors in accordance with clause 16.4.2.
After 16.4.1, insert clause 16.4.2 as follows: 16.4.2 For buried rainwater tanks and partially buried rainwater tanks without connection to a drinking water supply or with direct or indirect connections to a drinking water supply, a dual-check valve may be used in lieu of a testable device for Containment protection and Zone protection where it has been determined by risk assessment that—
the risk to tank rainwater quality from air pollution is low; and
the risk to tank rainwater quality from groundwater and/or surface water contamination is low. In assessing this risk the permeability of the tank and piping materials and joints to groundwater contaminants should be addressed; and
precautions in the design and installation of the rainwater collection system have been taken to reduce impacts to tank rainwater quality from the roof collection and delivery system. Such measures include, but are not restricted to, appropriate materials, gutter guards, filters, first flush devices, dry inlets, guards to exclude vermin and mosquitoes, and the quality of tank maintenance programs; and
precautions in the design and installation of the rainwater tank have been taken to reduce impacts to tank rainwater quality from groundwater and surface water pollution. Such measures include, but are not limited to—
location and topography; and
structural integrity of the tank including installation factors such as bedding, embedment, compaction and geotechnical specifications; and
water tightness of tank including all penetrations, connections, access covers and joints; and
ingress of vermin through the overflow e.g. by provision of a reflux valve, self-sealing valve, trap check valve; and
the risk assessment results must be submitted to the authority having jurisdiction.
Changed in NCC 2025. See NCC 2025 Volume Three SA B5D6, or show what changed.
Delete clause B5D6 and insert SA B5D6 as follows: (1) Protection of drinking water services from rainwater must be in accordance with AS/NZS 3500.1(2018) Clause 16.4 and Table 16.4 Part B5 Cross connection control with the additions; After 16.4, insert clause 16.4.1 as follows: 16.4.1 following variations. (2) When drinking water is used to top up a rainwater tank or supplement a rainwater service using a change-over device — It must be assigned a hazard rating based on the rainwater tank location. high hazard for buried rainwater tanks low hazard for partially buried rainwater tanks low hazard for above-ground rainwater tanks. A reduction of the Hazard Rating listed in table 16.4 for a buried rainwater tank to low may be permitted following a risk assessment of the design and installation of the rainwater tank and other environmental factors in accordance with clause 16.4.2. After 16.4.1, insert clause 16.4.2 as follows: 16.4.2 For buried rainwater tanks and partially buried rainwater tanks without connection to a drinking water supply or with direct or indirect connections to a drinking water supply, a dual-check valve may be used in lieu of a testable device for Containment protection and Zone protection where it has been determined by risk assessment that — the risk to tank rainwater quality from air pollution … assessment results must be submitted to the authority having jurisdiction.
Removed words are struck through; added words are highlighted. Comparison of the text only.