S1C2 Rating
Specification 1 Fire-resistance of building elements · NCC 2019: Sch. 5: 2
A building element meets the requirements of this Specification if—
it is listed in, and complies with Tables S1C2a, S1C2b, S1C2c, S1C2d, S1C2e, S1C2f, S1C2g, S1C2h, S1C2i, S1C2j, S1C2k, S1C2l, S1C2m or S1C2n of this Specification as applicable; or
it is identical with a prototype that has been submitted to the Standard Fire Test, or an equivalent or more severe test, and the FRL achieved by the prototype without the assistance of an active fire suppression system is confirmed in a report from an Accredited Testing Laboratory which—
describes the method and conditions of the test and the form of construction of the tested prototype in full; and
certifies that the application of restraint to the prototype complied with the Standard Fire Test; or
it differs in only a minor degree from a prototype tested under (b) and the FRL attributed to the building element is confirmed in a report from an Accredited Testing Laboratory which—
certifies that the building element is capable of achieving the FRL despite the minor departures from the tested prototype; and
describes the materials, construction and conditions of restraint which are necessary to achieve the FRL; or
it is designed to achieve the FRL in accordance with—
AS/NZS 2327, AS 4100 and AS/NZS 4600 if it is a steel or composite structure; or
AS 3600 if it is a concrete structure; or
AS 1720.4 if it is a timber element other than fire-protected timber; or
AS 3700 if it is a masonry structure; or
the FRL is determined by calculation based on the performance of a prototype in the Standard Fire Test and confirmed in a report in accordance with S1C3; or
for fire-protected timber, it complies with Specification 10 where applicable.
Table S1C2a FRLs deemed to be achieved by walls — masonry
Masonry type
Minimum thickness (mm) of principal material for FRLs
60/60/60
90/90/90
120/120/120
180/180/180
240/240/240
Ashlar
-
-
-
-
300
Calcium silicate
See clause S1C2(d)(iv)
Concrete
Fired clay
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table S1C2b FRLs deemed to be achieved by walls — concrete
Concrete type
Minimum thickness (mm) of principal material for FRLs
60/60/60
90/90/90
120/120/120
180/180/180
240/240/240
No fines
-
-
-
150
300
Prestressed
See clause S1C2(d)(iv)
Reinforced
Plain
-
-
-
150
170
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table S1C2c FRLs deemed to be achieved by walls — gypsum
Gypsum type
Minimum thickness (mm) of principal material for FRLs
60/60/60
90/90/90
120/120/120
180/180/180
240/240/240
Solid gypsum blocks
75
90
100
110
125
Gypsum — perlite or gypsum vermiculite-plaster on metal lath and channel (non-loadbearing walls only)
50
50
65
-
-
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table S1C2d FRLs deemed to be achieved by concrete columns
Column type
Minimum thickness (mm) of principal material for FRLs
60/60/60
90/90/90
120/120/120
180/180/180
240/240/240
Prestressed
See clause S1C2(d)(ii)
Reinforced
Table S1C2e FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on not more than 3 sides
Fire protection
Minimum thickness (mm) of principal material for FRLs
60/60/60
90/90/90
120/120/120
180/180/180
240/240/240
Concrete cast in-situ — loadbearing
25
30
40
55
75
Concrete cast in-situ — non-loadbearing unplastered
25
30
40
50
75
Concrete cast in-situ — non-loadbearing plastered 13 mm
25
25
30
40
50
Gypsum cast in-situ
-
-
-
-
50
Gypsum — perlite or gypsum-vermiculite plaster—sprayed to contour
20
25
35
50
55
Gypsum — perlite or gypsum-vermiculite plaster—sprayed on metal lath
20
20
25
35
45
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table S1C2f FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 3 sides and with column spaces filled
Fire protection
Minimum thickness (mm) of principal material for FRLs
60/60/60
90/90/90
120/120/120
180/180/180
240/240/240
Solid calcium-silicate masonry
50
50
50
50
65
Solid clay masonry
50
50
50
65
90
Solid concrete masonry
50
50
50
65
90
Solid gypsum blocks
50
50
50
50
65
Hollow terracotta blocks — plastered 13 mm
50
50
50
65
90
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table S1C2g FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 3 sides and with column spaces unfilled
Fire protection
Minimum thickness (mm) of principal material for FRLs
60/60/60
90/90/90
120/120/120
180/180/180
240/240/240
Solid calcium-silicate masonry
50
50
50
-
-
Solid clay masonry
50
50
65
-
-
Solid concrete masonry
50
50
65
-
-
Solid gypsum blocks
50
50
50
-
-
Hollow terracotta blocks — plastered 13 mm
50
50
65
-
-
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table S1C2h FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides
Fire protection
Minimum thickness (mm) of principal material for FRLs
60/–/–
90/–/–
120/–/–
180/–/–
240/–/–
Concrete cast in-situ — loadbearing
25
40
45
65
90
Concrete cast in-situ — non-loadbearing unplastered
35
30
40
50
65
Concrete cast in-situ — non-loadbearing plastered 13 mm
25
25
30
40
50
Gypsum cast in-situ
-
-
-
-
50
Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour
25
30
40
55
65
Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath
20
20
30
40
50
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table S1C2i FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides and with column spaces filled
Fire protection
Minimum thickness (mm) of principal material for FRLs
60/–/–
90/–/–
120/–/–
180/–/–
240/–/–
Solid calcium-silicate masonry
50
50
50
65
75
Solid clay masonry
50
50
50
75
100
Solid concrete masonry
50
50
50
75
100
Solid gypsum blocks
50
50
50
65
75
Hollow terracotta blocks — plastered 13 mm
50
50
50
75
100
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table S1C2j FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides and with column spaces unfilled
Fire protection
Minimum thickness (mm) of principal material for FRLs
60/–/–
90/–/–
120/–/–
180/–/–
240/–/–
Solid calcium-silicate masonry
50
50
50
-
-
Solid clay masonry
50
50
65
-
-
Solid concrete masonry
50
50
65
-
-
Solid gypsum blocks
50
50
50
-
-
Hollow terracotta blocks — plastered 13 mm
50
50
65
-
-
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table S1C2k FRLs deemed to be achieved by concrete beams
Concrete type
Minimum thickness (mm) of principal material for FRLs
60/–/–
90/–/–
120/–/–
180/–/–
240/–/–
Prestressed
See clause S1C2(d)(ii)
Reinforced
Table S1C2l FRLs deemed to be achieved by hot-rolled steel beams (including an open-web joist, girder, truss, etc.) exposed on no more than 3 sides
Fire protection
Minimum thickness (mm) of principal material for FRLs
60/–/–
90/–/–
120/–/–
180/–/–
240/–/–
Concrete — cast in-situ
25
30
40
50
65
Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour
20
25
35
50
55
Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath
20
20
25
35
45
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table S1C2m FRLs deemed to be achieved by hot-rolled steel beams (including an open-web joist, girder, truss, etc.) exposed on 4 sides
Fire protection
Minimum thickness (mm) of principal material for FRLs
60/–/–
90/–/–
120/–/–
180/–/–
240/–/–
Concrete — cast in-situ
25
40
45
60
90
Gypsum — p
Tables
- Table S1C2a FRLs deemed to be achieved by walls — masonry
- Table S1C2b FRLs deemed to be achieved by walls — concrete
- Table S1C2c FRLs deemed to be achieved by walls — gypsum
- Table S1C2d FRLs deemed to be achieved by concrete columns
- Table S1C2e FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on not more than 3 sides
- Table S1C2f FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 3 sides and with column spaces filled
- Table S1C2g FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 3 sides and with column spaces unfilled
- Table S1C2h FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides
- Table S1C2i FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides and with column spaces filled
- Table S1C2j FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides and with column spaces unfilled
- Table S1C2k FRLs deemed to be achieved by concrete beams
- Table S1C2l FRLs deemed to be achieved by hot-rolled steel beams (including an open-web joist, girder, truss, etc.) exposed on no more than 3 sides
- Table S1C2m FRLs deemed to be achieved by hot-rolled steel beams (including an open-web joist, girder, truss, etc.) exposed on 4 sides
- Table S1C2n FRLs deemed to be achieved by floor, roof or ceiling
Changed in NCC 2025. See NCC 2025 Volume Three S1C2, or show what changed.
A building element meets the requirements of this Specification if … — perlite or gypsum vermiculite-plaster on metal lath and channel (non-loadbearing (non-load bearing walls only) 50 50 65 - - Table Notes For … FRLs 60/60/60 90/90/90 120/120/120 180/180/180 240/240/240 Concrete cast in-situ — loadbearing load bearing 25 30 40 55 75 Concrete cast in-situ — non-loadbearing non-load bearing unplastered 25 30 40 50 75 Concrete cast in-situ — non-loadbearing non-load bearing plastered 13 mm 25 25 30 40 50 Gypsum cast … FRLs 60/–/– 90/–/– 120/–/– 180/–/– 240/–/– Concrete cast in-situ — loadbearing load bearing 25 40 45 65 90 Concrete cast in-situ — non-loadbearing non-load bearing unplastered 35 25 30 40 50 65 Concrete cast in-situ — non-loadbearing non-load bearing plastered 13 mm 25 25 30 40 50 Gypsum cast … 240/–/– Concrete — cast in-situ 25 40 45 60 90 Gypsum — p Gyp
Removed words are struck through; added words are highlighted. Comparison of the text only.