Table · NCC 2022 Volume Three

Table S1C2m FRLs deemed to be achieved by hot-rolled steel beams (including an open-web joist, girder, truss, etc.) exposed on 4 sides

Specification 1 Fire-resistance of building elements

Open Table S1C2m on NCC Online ↗
Fire protectionMinimum thickness (mm) of principal material for FRLs
60/–/–90/–/–120/–/–180/–/–240/–/–
Concrete — cast in-situ2540456090
Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour2030405565
Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath2020354050

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table for S1C2 Rating

Same wording in NCC 2025 Volume Three. See NCC 2025 Volume Three Table S1C2m.