Specification clause · NCC 2022 Volume Three

S41C5 Zone protection

Specification 41 Cross-connection hazards · NCC 2019: BS5.1.5

Open S41C5 on NCC Online ↗

(1) The following are Low Hazard for the purpose of zone protection:

Fire-fighting water storage tanks without chemical additives.

Food storage tanks, vats or vessels.

Hair salon basins or troughs.

Type B irrigation systems.

Water filtration equipment.

(2) The following are Medium Hazard for the purpose of zone protection:

Type C irrigation systems.

Beauty spas and foot salons.

(3) The following are High Hazard for the purpose of zone protection:

Photographic laboratories.

Aircraft facilities.

Secondary school laboratories, including fume cupboards.

Dental and medical procedure rooms and equipment using drinking water.

Clean-in-place systems.

Commercial laundries.

Cooling or heating systems with recirculating water.

Dockside facilities.

Drinking nipples and troughs (agricultural).

Food preparation or food storage tanks, vats or vessels.

Vats and vessels (clean-in-place systems).

In a Class 9 building—

dissecting rooms; and

utility rooms which contain fixtures other than hand basins; and

operating theatres.

Industrial and teaching laboratories.

Industrial process water that has been recirculated.

Mortuary equipment used in funeral parlours, mortuaries and autopsy areas.

Sanitary dump points.

Tanks, vats or vessels associated with electroplating, degreasing, descaling, stripping, pickling, dipping or the like.

Type D irrigation systems injected with fertilisers, herbicides, nematicides, insecticides or weedicides.