Specification clause · NCC 2022 Volume Three

S41C4 Individual protection

Specification 41 Cross-connection hazards · NCC 2019: BS5.1.4

Open S41C4 on NCC Online ↗
Varied in VIC. Check the variation for your state.

(1) The following are Low Hazard for the purpose of individual protection:

Carbonated drink dispensing machines.

Drinking fountains and bottle fillers.

Coils and jackets in heat exchangers, in sealed and non-toxic environments only.

Drink dispensing equipment including vending machines and coffee machines.

External hose taps, with no hazards within 18 m.

Fixtures used for ablutions including baths, basins, showers and bidettes with a minimum 25 mm air gap.

Toilet douche seats where the outlet in all positions is at least 25 mm above the overflow level of the pan.

Fixtures used for food preparation, including sinks.

Flexible connections over domestic fixtures.

Haemodialysis machines in Class 1, Class 2 and Class 10 buildings.

Hair salon basins or troughs.

In-line water softeners and filters.

Photographic processing machines without developer mixing.

Emergency eye wash and shower stations for use with drinking water.

Food preparation or food storage tanks, vats or vessels (without clean-in-place systems).

(2) The following are Medium Hazard for the purpose of individual protection:

Chemical dispensers (low toxicity).

Dental consoles.

(3) The following are High Hazard for the purpose of individual protection:

Chlorinators.

Coils and jackets in heat exchangers, in unsealed and toxic environments.

Steam calorifiers.

Steam boilers.

Antibiotic injectors (agricultural).

Bidets and toilet douche seats where the outlet in any position is not 25 mm above the overflow level of the pan.

Bidettes installed without a minimum 25 mm air gap.

Handheld bidet hoses and trigger sprays.

Chemical dispensers (high toxicity).

Cooling towers.

Demineralising equipment using ion-exchange resins with acid and alkali regeneration.

Equipment used for handling, mixing, measuring and processing chemical and microbiological substances.

Fogging and cleaning sprays with chemical injection or additives.

Mixing of chemicals.

Pan washing apparatus.

Photographic developers with drinking water supply rinse tanks or mixing facilities.

Plants with auxiliary non-drinking water supplies.

Type D irrigation system injected with fertilisers, herbicides, nematicides, insecticides or weedicides.

Weed and pest spraying and water cartage tanks.

Portable and mobile tankers.

Placenta / surgical waste disposal units.

Food preparation or food storage tanks, vats or vessels (with clean-in-place systems).

Not in NCC 2025. No S41C4 in NCC 2025 Volume Three.

State and territory variations all clauses side by side →

Defined terms used