Tasmania variation · NCC 2022 Volume Three

TAS C4D13 Portable grease interceptor appliances

TAS Part C4 On-site liquid trade waste systems

Open on NCC Online ↗

(1) The capacity of a portable grease interceptor must be authorised by the Permit Authority.

(2) A portable grease interceptor must contain a permanently fixed, ridged baffle constructed of a minimum—

6 mm unplasticised polyvinyl chloride (PVC-U); or

0.79 mm galvanised sheet steel; or

0.63 mm copper sheet; or

0.63 mm of 316 stainless steel; or

Other authorised material.

(3) A portable grease interceptor must be provided with airtight covers using lever clips.

(4) Ventilation of portable grease interceptors must—

be extended to open air; and

comply with AS/NZS 3500.2.

(5) A portable grease interceptor must be located in a position that enables ready access for maintenance and inspection.

(6) A portable grease interceptor must be protected from direct sunlight.

Exemptions

Where the Permit Authority has not specified the capacity of a grease interceptor in accordance with C4D13(1), it must be—

equivalent to the maximum hourly discharge; and

no less than 100 litres below the outlet.

Changed in NCC 2025. See NCC 2025 Volume Three TAS C4D13, or show what changed.

Delete clause C4D13 and insert TAS C4D13 as follows: (1) The capacity of a portable grease interceptor must be … discharge; and no less than 100 litres below the outlet.