TAS C4D19 Settling tanks
TAS Part C4 On-site liquid trade waste systems
(1) The capacity of a settling tank must be authorised by the Permit Authority.
(2) The settling tank and baffles are to be constructed of a minimum—
6 mm unplasticised polyvinyl chloride (PVC-U); or
0.79 mm galvanised sheet steel; or
0.63 mm copper sheet; or
0.63 mm 316 stainless steel; or
other authorised acid and alkali resistant material.
(3) The diameter of the outlet pipe must be—
DN 100 when the outlet size is DN 100; or
a minimum one size larger than the inlet pipe.
(4) A settling tank must be located in a position that enables ready access for maintenance, sampling and inspection.
(5) Where a settling tank is to be located below ground level, it must—
be surrounded with concrete walls and base with a minimum thickness of 100 mm; and
omit the 25 mm sampling valve; and
have a minimum DN 100 outlet pipe located no deeper than 600 mm below surface level; and
have the outlet pipe connected to a disconnector gully fitted with a loos fitting grate or screwed cap.
Exemptions
Where the Permit Authority has not specified the capacity of a settling tank in accordance with C4D19(1), it must be—
equivalent to the maximum hourly discharge; and
no less than 72 litres, below the outlet.