TAS C4D6 Ventilation
TAS Part C4 On-site liquid trade waste systems
(1) Where airtight covers are fitted, trade waste appliances must be vented with a minimum DN 50 vent.
(2) Outlet ventilation is to be provided by either a—
DN 100 riser from a disconnector gully outside a building; or
DN 50 vent from a disconnector gully at the outlet of a non-portable appliance inside a building; or
DN 50 vent from a DN 80 trap riser at the outlet of a portable appliance, inside a building.
(3) Trade waste appliance vents and outlet vents may be combined inside a building.
(4) Ventilation must be provided in accordance with AS/NZS 3500.2.
Changed in NCC 2025. See NCC 2025 Volume Three TAS C4D6, or show what changed.
Delete clause C4D6 and insert TAS C4D6 as follows: (1) Where airtight covers are fitted, trade waste appliances must … (4) Ventilation must be provided in accordance with AS/NZS 3500.2.
Removed words are struck through; added words are highlighted. Comparison of the text only.