Tasmania variation · NCC 2022 Volume Three

TAS C4D6 Ventilation

TAS Part C4 On-site liquid trade waste systems

Open on NCC Online ↗

(1) Where airtight covers are fitted, trade waste appliances must be vented with a minimum DN 50 vent.

(2) Outlet ventilation is to be provided by either a—

DN 100 riser from a disconnector gully outside a building; or

DN 50 vent from a disconnector gully at the outlet of a non-portable appliance inside a building; or

DN 50 vent from a DN 80 trap riser at the outlet of a portable appliance, inside a building.

(3) Trade waste appliance vents and outlet vents may be combined inside a building.

(4) Ventilation must be provided in accordance with AS/NZS 3500.2.