VIC B4D2 General requirements
Part B4 Fire-fighting water services · varies B4D2 General requirements
Delete clause B4D2 and insert VIC B4D2 as follows:
(1) Fire-fighting water services for Class 2 to Class 9 buildings and structures must comply with the requirements of Part E1 of Volume One of the NCC.
(2) The installation of a fire-fighting water service must be in accordance with AS/NZS 3500.1.
(3) When installed in Class 1 or Class 10 buildings and structures, an automatic fire sprinkler system must be in accordance with AS 2118.1, AS 2118.4, or AS 2118.5 as appropriate.
(4) Fire-fighting water service work must be in accordance with—
AS/NZS 1530.3,
AS 4118.1.1,
AS 4118.1.2,
AS 4118.1.3,
AS 4118.1.4,
AS 4118.1.5,
AS 4118.1.6,
AS 4118.1.7,
AS 4118.1.8,
AS 2941,
AS 2118.2,
AS 2118.3,
AS 2118.8,
AS 2118.10; and
AS 1851 as appropriate.
Changed in NCC 2025. See NCC 2025 Volume Three VIC B4D2, or show what changed.
Delete clause B4D2 and insert VIC B4D2 as follows: (1) … water service must be in accordance with AS/NZS 3500.1. (3) When installed in Class 1 or Class 10 buildings and structures, an automatic fire sprinkler system must be in accordance with AS 2118.1, AS 2118.4, or AS 2118.5 as appropriate. (4) Fire-fighting water service work must be in accordance with — AS/NZS 1530.3, AS 4118.1.1, AS 4118.1.2, AS 4118.1.3, AS 4118.1.4, AS 4118.1.5, AS 4118.1.6, AS 4118.1.7, AS 4118.1.8, AS 2941, AS 2118.2, AS 2118.3, AS 2118.8, AS 2118.10; and AS 1851 as appropriate. 1851.