Victoria variation · NCC 2022 Volume Three

VIC B4D2 General requirements

Part B4 Fire-fighting water services · varies B4D2 General requirements

Open on NCC Online ↗

Delete clause B4D2 and insert VIC B4D2 as follows:

(1) Fire-fighting water services for Class 2 to Class 9 buildings and structures must comply with the requirements of Part E1 of Volume One of the NCC.

(2) The installation of a fire-fighting water service must be in accordance with AS/NZS 3500.1.

(3) When installed in Class 1 or Class 10 buildings and structures, an automatic fire sprinkler system must be in accordance with AS 2118.1, AS 2118.4, or AS 2118.5 as appropriate.

(4) Fire-fighting water service work must be in accordance with—

AS/NZS 1530.3,

AS 4118.1.1,

AS 4118.1.2,

AS 4118.1.3,

AS 4118.1.4,

AS 4118.1.5,

AS 4118.1.6,

AS 4118.1.7,

AS 4118.1.8,

AS 2941,

AS 2118.2,

AS 2118.3,

AS 2118.8,

AS 2118.10; and

AS 1851 as appropriate.

Changed in NCC 2025. See NCC 2025 Volume Three VIC B4D2, or show what changed.

Delete clause B4D2 and insert VIC B4D2 as follows: (1) … water service must be in accordance with AS/NZS 3500.1. (3) When installed in Class 1 or Class 10 buildings and structures, an automatic fire sprinkler system must be in accordance with AS 2118.1, AS 2118.4, or AS 2118.5 as appropriate. (4) Fire-fighting water service work must be in accordance with — AS/NZS 1530.3, AS 4118.1.1, AS 4118.1.2, AS 4118.1.3, AS 4118.1.4, AS 4118.1.5, AS 4118.1.6, AS 4118.1.7, AS 4118.1.8, AS 2941, AS 2118.2, AS 2118.3, AS 2118.8, AS 2118.10; and AS 1851 as appropriate. 1851.