VIC S41C6 Containment protection
Specification 41 Cross-connection hazards · varies S41C6 Containment protection
Delete clause S41C6 and insert VIC S41C6 as follows:
(1) The following are Low Hazard for the purpose of containment protection:
A water service provided to a Class 1, Class 2, Class 7a or Class 10 building where—
not more than 12 persons reside; and
the building may only use non-commercial amounts of cleaning products.
Premises served by a rainwater harvesting system, not including any rainwater storage tanks that are buried tanks.
Properties with only a drinking water service provided by a Network Utility Operator.
Properties served by a Network Utility Operator's recycled water supply.
(2) The following are Medium Hazard for the purpose of containment protection:
A water service provided to a Class 3, Class 4, Class 5, Class 6 or Class 7b building where chemicals are not stored.
A water service provided to a property that has—
other non-drinking water services; or
a separate fire water service.
(3) The following are High Hazard for the purpose of containment protection:
A water service provided to a Class 7b building where chemicals may be stored.
A water service provided to a Class 8 or Class 9 building.
A water service provided to a property used for commercial agriculture, farming, turf irrigation, industrial, processing or chemical industries.
A water service provided to a property that has non-drinking water services from multiple sources with potential for health related contamination.
Applications
Medium Hazard properties for the purpose of containment protection include the following—
Caravan parks.
Food and beverage processing plants.
Marinas.
Premises that are connected to a grey water re-use system or a reticulated and disinfected reclaimed water system.
Public swimming pools.
High Hazard properties for the purpose of containment protection include the following—
Abattoirs.
Car and plant washing facilities.
Chemical laboratories.
Chemical plants.
Factories using, processing or manufacturing toxic chemicals.
Hospitals, mortuaries, dental surgeries, clinics or day surgeries and the like containing patient care areas such as an operating theatre, minor procedures consultation room, resuscitation, intensive care and coronary care.
Metal finishing plants.
Pathology laboratories.
Petroleum processing and storage plants and facilities.
Piers, docks and other waterfront facilities.
Premises where access to conduct inspections is restricted.
Sanitary depots.
Sewerage treatment plants and sewerage lift stations.
Universities.
Premises containing wastewater dump points.
Industrial processing.
Chemical industries.