Performance Requirement · NCC 2022 Volume Two

H7P6 Private bushfire shelters

Part H7 Ancillary provisions and additional construction requirements · NCC 2019: P2.7.6

Open H7P6 on NCC Online ↗

A private bushfire shelter must be designed and constructed to provide a tenable environment for occupants during a design bushfire with an annual probability of exceedance not more than 1:200 years, appropriate to the—

location of the private bushfire shelter relative to fire hazards including—

predominant vegetation; and

adjacent buildings and structures; and

allotment boundaries; and

other combustible materials; and

occupancy of the private bushfire shelter; and

bushfire intensity having regard for the bushfire attack level; and

fire intensity from adjacent buildings and structures, allotment boundaries and other combustible materials; and

ready access to the private bushfire shelter from the associated dwelling and occupant egress after the fire; and

tenability within the private bushfire shelter for the estimated maximum period of occupancy; and

generation of smoke, heat and toxic gases from materials used to construct the private bushfire shelter; and

structural and fire loads and actions to which it may reasonably be subjected, appropriate to—

the topography between the private bushfire shelter and the predominant vegetation or other fire hazards; and

the distance between the private bushfire shelter and the predominant vegetation or other fire hazards; and

the size of the potential fire source and fire intensity; and

wind loading; and

potential impact from debris such as falling tree limbs; and

degree of external signage identifying the location of the private bushfire shelter; and

degree of internal signage identifying the design capacity and maximum period of occupancy; and

degree of occupant awareness of outside environmental conditions; and

degree of essential maintenance.

Applications

H7P6 only applies to a Class 10c building.

Notes

NCC Volume Two and the ABCB Housing Provisions do not contain any Deemed-to-Satisfy Provisions for H7P6, however the ABCB Performance Standard for Private Bushfire Shelters contains guidance for H7P6.

Same wording in NCC 2025 Volume Two. See NCC 2025 Volume Two H7P6.