Specification clause · NCC 2022 Volume Two
S2C21 Filling of column spaces
Specification 2 Descriptions of elements referred to in Specification 1 · NCC 2019: Sch. 5 (Annex): 9
(1) The spaces between the fire-protective material and the steel (and any re-entrant parts of the column itself) must be filled solid with a fire-protective material like concrete, gypsum or grout.
(2) The insides of hollow sections, including pipes, need not be filled.