Table · NCC 2022 Volume Two

Table S1C2i FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides and with column spaces filled

Specification 1 Fire-resistance of building elements

Open Table S1C2i on NCC Online ↗
Fire protectionMinimum thickness (mm) of principal material for FRLs
60/–/–90/–/–120/–/–180/–/–240/–/–
Solid calcium-silicate masonry5050506575
Solid clay masonry50505075100
Solid concrete masonry50505075100
Solid gypsum blocks5050506575
Hollow terracotta blocks — plastered 13 mm50505075100

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table for S1C2 Rating

Same wording in NCC 2025 Volume Two. See NCC 2025 Volume Two Table S1C2i.