Table · NCC 2022 Volume Two

Table S1C2h FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides

Specification 1 Fire-resistance of building elements

Open Table S1C2h on NCC Online ↗
Fire protectionMinimum thickness (mm) of principal material for FRLs
60/–/–90/–/–120/–/–180/–/–240/–/–
Concrete cast in-situ — loadbearing2540456590
Concrete cast in-situ — non-loadbearing unplastered3530405065
Concrete cast in-situ — non-loadbearing plastered 13 mm2525304050
Gypsum cast in-situ----50
Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour2530405565
Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath2020304050

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table for S1C2 Rating

Changed in NCC 2025. See NCC 2025 Volume Two Table S1C2h, or show what changed.

Fire protection | Minimum thickness (mm) of principal material for FRLs 60/–/– | 90/–/– | 120/–/– | 180/–/– | 240/–/– Concrete cast in-situ — loadbearing load bearing | 25 | 40 | 45 | 65 | 90 Concrete cast in-situ — non-loadbearing non-load bearing unplastered | 35 25 | 30 | 40 | 50 | 65 Concrete cast in-situ — non-loadbearing non-load bearing plastered 13 mm | 25 | 25 | 30 | … table, each element must meet the requirements of Specification 2.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Defined terms used