Western Australia variation · NCC 2022 Volume Two

WA H1D7 Roof and wall cladding

Part H1 Structure · varies H1D7 Roof and wall cladding

Open on NCC Online ↗

Delete clause H1D7 and insert WA H1D7 as follows:

(1) Diagrams depicting relevant roofing and supporting members and associated terminology used to describe them are set out in Figure H1D7a and Figure H1D7b.

(2) Performance RequirementH1P1 is satisfied for sheet roofing if it complies with one or a combination of the following:

Metal roofing:

AS 1562.1; and

in wind regions B, C and D in accordance with Figure 2.2.3 in Section 2 of the ABCB Housing Provisions (cyclonic areas), metal roof assemblies, their connections and immediate supporting members must be capable of remaining in position notwithstanding any permanent distortion, fracture or damage that might occur in the sheet or fastenings under the pressure sequences A to G defined in Table H1D7.

Plastic sheet roofing: AS 1562.3.

Metal sheet roofing: Part 7.2 of the ABCB Housing Provisions, provided the building is located in an area with a wind class of not more than N3.

(3) Performance RequirementH1P1 is satisfied for roof cladding if it complies with one or a combination of the following:

Terracotta, fibre-cement and timber slates and shingles: AS 4597.

For roof tiles—

AS 2050; or

Part 7.3 of the ABCB Housing Provisions, provided—

the building is located in an area with a wind class of not more than N3; and

the roof tiles comply with AS 2049; and

the roof has a pitch of not less than 15 degrees and not more than 35 degrees.

(4) Performance RequirementH1P1 is satisfied for timber and composite wall cladding if it is designed and constructed in accordance with—

for autoclaved aerated concrete wall cladding, AS 5146.1; or

for wall cladding, Part 7.5 of the ABCB Housing Provisions.

(5) Performance RequirementH1P1 is satisfied for a metal wall cladding if it is designed and constructed in accordance with AS 1562.1.

Table H1D7 Low-High-Low pressure sequence

Sequence

Number of cycles

Load

A

4500

0 to 0.45 Pt

B

600

0 to 0.6 Pt

C

80

0 to 0.8 Pt

D

1

0 to 1.0 Pt

E

80

0 to 0.8 Pt

F

600

0 to 0.6 Pt

G

4500

0 to 0.45 Pt

Table Notes

Pt is the ultimate limit state wind pressure on internal and external surfaces as determined in accordance with AS/NZS 1170.2, modified by an appropriate factor for variability, as determined in accordance with Table B1 of AS/NZS 1170.0.

The rate of load cycling must be less than 3 Hz.

The single load cycle (sequence D) must be held for a maximum of 10 seconds.

Figure H1D7a Section of a typical sheet roof

Figure H1D7b Section of a typical tile roof

Not in NCC 2025. No WA H1D7 in NCC 2025 Volume Two.

The national clause